RED00202(R2) MANUAL

Manual and Technical Function 

Technical Description 

If breakdowns cost a lot of money and a service call is expensive, it is advisable to operate the power supply 
redundantly.  The  redundancy  module  RED00202  is  designed  for  applications  from  0Vdc  to  125Vdc.  The  DC 
outputs of two identical DC voltage sources are decoupled. The total load is equal to the individual load of each 
connected DC source. 
In  normal  operation,  the  total  load  is  distributed  evenly  among  the  connected  power  supplies.  If  one  of  the 
connected DC power sources fails, the other source takes over the entire load without causing a power failure in 
the system. The internal Power-ok relay (changeover contact) provides continuous control of the status of the 
connected power supplies. If one power supply fails, the relay indicates that the remaining power supply will take 
over. The low voltage detection Vu can be adjusted via the ADJ control potentiometer on the front panel. The 
over voltage detection Vo from the technical data table is set by the factory and cannot be changed. 

The DC input and the DC output are potential-free. The GND input of the RED00202 is only necessary for self-
supply. The voltage drop between DC input and DC output is between 500mV and 700mV (see table Technical 
Data). 

Current voltage graph 

Voltage control specification: 

The change-over contact of the control relay is at the left 
position when the input voltage V1in and V2in operate 
between Vu and Vo. The LED of each input lights green. 
The relay contact changes to the right position when the 
input voltages are either smaller Vu or larger Vo. 

The upper voltage margin Vo is fixed by the factory. The low 
voltage  detection  Vu  can  be  set  with  the  front  sided 
potentiometer (ADJ). The input to DC output power ratio is 
2x 1kWinput = 1x 1kWoutput, 1x 1kWinput = 1x 1kWoutput 

The  model  RED00202A  can  be  used  below  12Vdc.  Note 
that  the  DC-ok  relay  and  the  ADJ  potentiometer  will  not 
function  below  when  a  voltage  below  12Vdc  is  applied  to 
the inputs V1in & V2in. 

Temperature Derating

 

The maximum ambient temperature during operation is + 70°C. 

The measuring point is 50mm outside the device. 

Coating Option 

We offer the RED-series with optional coating. It is to be used in e.g., dusty, dirty, high humidity, or in awaiting 
quick temperature changes. Short circuit and corrosion at print board lines and at solder points can be 
prevented. The coat itself is a transparent acrylic resin. Peters SL 1306 N-FLZ (transparent) IEC60216-1 2001, 
IPC-CC-830B, UL listed as permanent coating File No.: E80315 , UL94V-0 

[email protected]

www.powersolve.co.uk

020321

Summary of Contents for RED00202A

Page 1: ...protected Monitoring relay floating Low voltage drop Screw terminals 16mm2 EN62368 1 Schottky barrier decoupling diodes Efficiency 97 Adjustable drop out voltage detection 20 C 70 C ambient temperature IP20 metal housing Models Voltage RED00202A R2 0 28Vdc RED02020B R2 36 60Vdc RED00202C R2 90 125Vdc sales powersolve co uk www powersolve co uk 020321 ...

Page 2: ...wer Good Relay Change over contact Relay contact load 48Vdc 500mA max Relay contact separation Protective electrical insulation 60Vdc Cooling Natural convection Ambient temperature 20 C 70 C Storage temperature 40 C 85 C Environment Humidity 95 non condensing 25 C climate class 3k3 pollution degree 2 ROHS 2011 65 EU EU 2015 863 REACH EG No 1907 2006 EMI EN55032 class B EN61000 6 3 EMS EN61000 6 2 ...

Page 3: ...p between DC input and DC output is between 500mV and 700mV see table Technical Data Current voltage graph Voltage control specification The change over contact of the control relay is at the left position when the input voltage V1in and V2in operate between Vu and Vo The LED of each input lights green The relay contact changes to the right position when the input voltages are either smaller Vu or...

Page 4: ...ED00202 Stable metal aluminium housing IP20 To allow adequate convection a free air space of 50mm top bottom and 10mm sidewalls is required and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the RED One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60715 It is easy to mount dismount ...

Page 5: ... H4 0 12 12mm H4 0 20 GDR 14mm 6 0mm H6 0 20 12mm H6 0 20 SW 14mm 10 0mm H10 0 12 12mm H10 0 22 EB 15mm The length of ferrules is to be chosen depending on the rated voltage The outside diameter of the plastic collar should not be larger than the pitch P Ordering Information Ordering Codes Product Code Volt Power Information Article Number RED00202A R2 0 28Vdc 1000W below 12Vdc is the DC OK relay ...

Page 6: ...ng bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things Warning Non compliance these warnings can result in fire and serious injury or death 1 Allow neat and professional cabling 2 Never open nor try to repair the unit Inside are dangero...