Powersolve RED00202A Manual Download Page 2

RED00202(R2) MANUAL

Technical Data Table 

Model 

RED00202A 

RED00202B 

RED00202C 

2 Channel Inputs 

V1in / V2in 

V1in / V2in 

V1in / V2in 

1 Channel Output 

Vout 

Vout 

Vout 

DC-Input Voltage

+0Vdc - +28Vdc

+36Vdc - +60Vdc

+90Vdc - +125Vdc

DC-Input Upper Margin Vo

fix +36V ± 5% 

fix +75V ± 5% 

fix +140V ± 5% 

Hysteresis Vo 

~1.5V 

~1.5V 

~1.5V 

Drop-Out Voltage Set Range 

+8Vdc - +28Vdc

+24Vdc - +60Vdc

+60Vdc - +135Vdc

Low-Rate Hysteresis Vu 

~1.5V 

~1.5V 

~1.5V 

Maximum Input Current 

2x 50A (2x 1000W) 

2x 28A (2x 1000W) 

2x 9,1A (2x 1000W) 

Maximum Output Current 

1x 50A (1x 1000W total) 

1x 28A (1x 1000W total) 

1x 9,1A (1x 1000W total) 

Voltage Drop, Input to Output 

500mV typical 

600mV typical 

700mV typical 

DC Input 

Floating 

DC Output 

Floating 

Power Good Relay 

Change over contact 

Relay contact load 

48Vdc 500mA max. 

Relay contact separation 

Protective electrical insulation 

60Vdc 

Cooling 

Natural convection 

Ambient temperature 

-20°C...+70°C

Storage temperature 

-40°C...+85°C

Environment 

Humidity 95% non-condensing @ 25°C, climate class. 3k3, pollution degree 2 

ROHS 

2011/65/EU, (EU)2015/863 

REACH 

EG No. 1907/2006 

EMI 

EN55032 class B, EN61000-6-3 

EMS 

EN61000-6-2 

Safety 

EN61010-1, EN61010-2-201, EN62368-1, EN60950-1, EN60204-1 

Protection Class I 

PE connection required 

Altitude in Operation 

3000m (9842 ft) above sea level 

MTBF (IEC61709) 

500000h (Meantime Between Failures: statistic time between failures after repairs) 

MTTF (IEC61709) 

175236 (Meantime To Failure: statistic time to ever fails) 

Dimensions (HxWxD) 

130x62x115mm 

Weight 

1kg 

Connectors 

Output Screw Terminal 4x AWG22 – AWG6 / 0,5 – 16mm² (+ + + - ) 

[email protected]

www.powersolve.co.uk

020321

Summary of Contents for RED00202A

Page 1: ...protected Monitoring relay floating Low voltage drop Screw terminals 16mm2 EN62368 1 Schottky barrier decoupling diodes Efficiency 97 Adjustable drop out voltage detection 20 C 70 C ambient temperature IP20 metal housing Models Voltage RED00202A R2 0 28Vdc RED02020B R2 36 60Vdc RED00202C R2 90 125Vdc sales powersolve co uk www powersolve co uk 020321 ...

Page 2: ...wer Good Relay Change over contact Relay contact load 48Vdc 500mA max Relay contact separation Protective electrical insulation 60Vdc Cooling Natural convection Ambient temperature 20 C 70 C Storage temperature 40 C 85 C Environment Humidity 95 non condensing 25 C climate class 3k3 pollution degree 2 ROHS 2011 65 EU EU 2015 863 REACH EG No 1907 2006 EMI EN55032 class B EN61000 6 3 EMS EN61000 6 2 ...

Page 3: ...p between DC input and DC output is between 500mV and 700mV see table Technical Data Current voltage graph Voltage control specification The change over contact of the control relay is at the left position when the input voltage V1in and V2in operate between Vu and Vo The LED of each input lights green The relay contact changes to the right position when the input voltages are either smaller Vu or...

Page 4: ...ED00202 Stable metal aluminium housing IP20 To allow adequate convection a free air space of 50mm top bottom and 10mm sidewalls is required and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the RED One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60715 It is easy to mount dismount ...

Page 5: ... H4 0 12 12mm H4 0 20 GDR 14mm 6 0mm H6 0 20 12mm H6 0 20 SW 14mm 10 0mm H10 0 12 12mm H10 0 22 EB 15mm The length of ferrules is to be chosen depending on the rated voltage The outside diameter of the plastic collar should not be larger than the pitch P Ordering Information Ordering Codes Product Code Volt Power Information Article Number RED00202A R2 0 28Vdc 1000W below 12Vdc is the DC OK relay ...

Page 6: ...ng bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things Warning Non compliance these warnings can result in fire and serious injury or death 1 Allow neat and professional cabling 2 Never open nor try to repair the unit Inside are dangero...

Reviews: