Powersolve RED00202A Manual Download Page 4

RED00202(R2) MANUAL

Connections and Signal Table 

Position 

Function 

Remarks 

V1in 

DC(+) voltage input 1 

Connect to (+) of the DC-source 1 

V2in 

DC(+) voltage input 2 

Connect to (+) of the DC-source 2 

Vout 

DC(+) voltage output 

Connect to (+) of the load 

GND 

Common GND 

Connect to (-) of the DC sources 1&2 and to the (-) of the connected load 

Relay 

Change over contact 

Left position indicates all DC-inputs are ok and operate between Vu and Vo 
Right position indicates that a DC-source fails or that it operates below Vu or 
above Vo 

V1in LED 

LED signal 

OFF = no voltage, YELLO = low voltage 

V1in LED 

LED signal 

OFF = no voltage, YELLO = low voltage 

ADJ 

Potentiometer 

Set the drop out voltage together for V1 and V1 

Mechanics & Installation Instruction of the RED00202 

Stable metal/aluminium housing IP20. To allow adequate convection, a free air space of 50mm (top/bottom) 
and 10mm (sidewalls) is required; and for active devices 15mm space from the sidewalls. For proper air 
convection it is necessary to install the RED. One can use the DIN-Rail installation (equipped standard) with our 
patented 35mm DIN-Rail bracket according to EN60715. It is easy to mount/dismount while snaping it onto the 
35mm DIN-Rail - no tools necessary. The housing screws are recommended for the GND-connection – do not 
remove them. For operation >60Vdc a GND-connection to PE is necessary to prevent from any kind of 
interferences to the supply system.

 

It is not allowed to install the RED00202 in other mounting direction then below drawings. 

 

natural convection 

>20 CFM

Mounting Instruction 

Bottom 

forced convection: 

To

De

vic

Bo

tto

Top 

Device

 

Bottom

Rail

D

e

v

ic

e

 

[email protected]

www.powersolve.co.uk

020321

Summary of Contents for RED00202A

Page 1: ...protected Monitoring relay floating Low voltage drop Screw terminals 16mm2 EN62368 1 Schottky barrier decoupling diodes Efficiency 97 Adjustable drop out voltage detection 20 C 70 C ambient temperature IP20 metal housing Models Voltage RED00202A R2 0 28Vdc RED02020B R2 36 60Vdc RED00202C R2 90 125Vdc sales powersolve co uk www powersolve co uk 020321 ...

Page 2: ...wer Good Relay Change over contact Relay contact load 48Vdc 500mA max Relay contact separation Protective electrical insulation 60Vdc Cooling Natural convection Ambient temperature 20 C 70 C Storage temperature 40 C 85 C Environment Humidity 95 non condensing 25 C climate class 3k3 pollution degree 2 ROHS 2011 65 EU EU 2015 863 REACH EG No 1907 2006 EMI EN55032 class B EN61000 6 3 EMS EN61000 6 2 ...

Page 3: ...p between DC input and DC output is between 500mV and 700mV see table Technical Data Current voltage graph Voltage control specification The change over contact of the control relay is at the left position when the input voltage V1in and V2in operate between Vu and Vo The LED of each input lights green The relay contact changes to the right position when the input voltages are either smaller Vu or...

Page 4: ...ED00202 Stable metal aluminium housing IP20 To allow adequate convection a free air space of 50mm top bottom and 10mm sidewalls is required and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the RED One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60715 It is easy to mount dismount ...

Page 5: ... H4 0 12 12mm H4 0 20 GDR 14mm 6 0mm H6 0 20 12mm H6 0 20 SW 14mm 10 0mm H10 0 12 12mm H10 0 22 EB 15mm The length of ferrules is to be chosen depending on the rated voltage The outside diameter of the plastic collar should not be larger than the pitch P Ordering Information Ordering Codes Product Code Volt Power Information Article Number RED00202A R2 0 28Vdc 1000W below 12Vdc is the DC OK relay ...

Page 6: ...ng bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things Warning Non compliance these warnings can result in fire and serious injury or death 1 Allow neat and professional cabling 2 Never open nor try to repair the unit Inside are dangero...

Reviews: