Powersmiths International Corp.
Toll Free: 1 800 747 9627
8958 Airport Rd,
Fax: 905 791 1493
ON. L6T 5T2
Cyberhawk-200M Installation
-
1 of 22 -
Doc. No: 202-003318-610 Rev A01
!
Cyberhawk-200M Installation Bulletin
Safety Notice
A potential
Shock and Injury Hazard
exists when working on electrical systems which could lead
to serious injury or even death if safety precautions are not observed. Only qualified competent
personnel who have been trained in and are familiar with the
Risk of Electric Shock
and burns
from
Plasma Arcs
should perform installation and maintenance on electrical systems. It is the sole
responsibility of the personnel
doing the work to be fully cognizant of all necessary safety
regulations and procedures and
be familiar with the installation instructions detailed in this
manual
.
FOR YOUR SAFETY, IT IS IMPERATIVE THAT THE POWER BE PROVEN DISCONNECTED
BEFORE ANY WORK ON OR PHYSICAL CONTACT TO ELECTRICAL CIRCUITS IS
ATTEMPTED: DO NOT ASSUME BUT CHECK ACROSS THE LINES AND TO GROUND WITH
AN APPROVED VOLTAGE INDICATING DEVICE AND ENSURE THAT THE POWER
SOURCE(S) DISCONNECTION DEVICES ARE LOCKED OUT.
WHEN WORKING IN CLOSE PROXIMITY TO LIVE INSTALLATIONS FOLLOW ALL SAFETY
REQUIREMENTS DEFINED IN NFPA 70E OR CSA Z462 WHICH WILL INCLUDE, BUT NOT
LIMITED TO, THE USE OF PROTECTIVE EQUIPMENT (PPE) (CLOTHING, INSULATED
GLOVES, SAFETY GOGGLES, ETC.). IT FURTHER RECOMMENDED THAT ALL METALLIC
OBJECTS (SUCH AS JEWELRY, WATCHES, CHAINS ETC.) BE REMOVED FROM THEIR
PERSON.
Symbols Used in this Manual
Risk of Electric Shock and/or ARC Flash Hazard: Life threatening voltages may be present with the
risk of ARC Flash in the event of an inadvertent short circuit.
Cautionary Safety Alert: Draws attention to particular cautionary notes which, though not life
threating, could result in injury or equipment damage if attention is not paid to the described
precaution.
Limits to use of this equipment
This equipment is designed for permanent installation to monitor electrical circuits to 250VAC or
600VAC, model specific. Refer to the specific model as defined in the specifications for the model
specific voltage limits and for the installation and environmental category.
The devices defined herein are intended to be used with defined current sensors; refer to the specific
sections of the manual for the approved accessories. Use of other unapproved current sensors may
compromise the safe operation of this instrument.
Devices and connections to the ancillary inputs and outputs (other than to external power) are
required to be insulated and isolated from mains voltages and must not exceed 32VAC (60VDC);
refer to relevant sections of this manual for additional notes and limits.
Protection is effected by double/reinforced insulation between the power and control/user circuits to
600V CATIII (UL61010-1) and by integral fusing for internal faults. Application of this equipment in a
manner not specified in this manual may compromise its inherent protection.
The equipment is insulated by double/reinforced insulation up to 600VAC CAT III (UL61010-1)
between the power inputs (L1, L2, L3, N) and the control and user circuits. The power input circuits
may be field ‘High Potential’ tested up to 2.5kVAC without damage.