6.2. Battery Power up / Shut Down Procedure
Each battery has an integrated DC circuit breaker to protect the battery in the event of a system fault and is
also used to power the battery ON and OFF.
Important:
If the power system has been shutdown or charging source removed, the battery should have its circuit
breaker cycled to the Off position within 48hrs to alleviate battery discharge from self discharge or system
standby discharge.
The below shut down procedure should be used in conjunction with the system shutdown procedure.
6.2.1. Battery Startup
The battery system should be started following the startup procedure supplied with the system.
The Eco Batteries do not provide an output voltage until they are turned on. In most cases powering on the
battery will be one of the first steps of starting your power system.
• Locate and ensure you main system Isolation point is OFF.
• Check all battery connections to be correctly installed.
• Individually (working in a systematical approach), turn battery circuit breakers to the ON position (cycle to
the right when looking at the front face of the battery face on).
• Main Status LED will illuminate indicating voltage is present at the battery terminals.