5.2.3. PEF6W-250B Installation
The PEF6W-250B is a BESS (Battery Energy Storage System) cabinets designed to house the PowerPlus
Energy batteries and connected PCE’s for charge and discharge. The cabinets are suitable to be installed
indoor or outdoor.
• The cabinet should be installed on level, solid surface. The surface should be concrete, brick, masonite
or similar.
• Securely mount the battery enclosure to the wall using appropriate fastening. Your fastening types will
vary depending on wall surface and sub-strait.
• The wall should be rated to support all equipment, including up to 342kg plus the weight of other PCE’s
and balance of system installed.
• The feet should be adjusted to level and stabilise the cabinet.
• Choose cable entry position to suit your application. Cable entry can be positioned anywhere around the
cabinet to suit the application.
• Ensure suitable glands or similar are used to protect the cables after forming cable entry hole. Glands are
not supplied and should be of the same or higher IP rating of the cabinet.
• Ensure all filings from forming holes are removed from cabinet.
• A Detachable gear plate is provided for the mounting of PCE’s and balance of system equipment.
• DC isolator, main DC busbar and all interconnecting battery cables are provided and should installed to
suit your layout inside the cabinet.
• Up to 6 Eco P Series batteries can be installed on the lower shelves.
• Using a 2 person lift, slide the batteries into the cabinet starting from the bottom shelf at the rear and
working your way to the front and the repeat on upper shelf.
• Connect corresponding Amphenol Surlok cables to batteries.
• The supplied fan assembly can have the fan removed and rotated to allow air to either be drawn into or
out of the cabinet. It can be positioned in either of the cabinet vent holes.
• The fans are 240V powered and come supplied with a temperature controlled thermostat that can be
adjusted and positioned to suit your installation.
Note: Batteries should be loaded from the rear of the cabinet working your way to the front. This ensures
the cabinet remains stable and weight is distributed closet to the wall.
Eco P Series Installation Manual V3.0
21/10/2021
Page
of
27