Automatic Flash Configuration
This configuration uses the existing residual AC voltage from the generator stator to
build the terminal voltage to a point that the automatic voltage regulator can take over
and perform its function.
Take special care to follow the wiring directions precisely! DO NOT use the
automatic flash configuration in conjunction with the battery flash configuration!
Note that the maximum input voltage to the AFM500X Automatic Flashing Module
is 240VAC!
DO NOT input 277VAC into the AFM500X!
Severe damage to the unit
will result! For use on 480V systems, either connect the regulator to the winding center
taps T7 and T8 or use a 480-240V step-down transformer.
NOTE:
Wiring from the AFM500X must ALWAYS be connected to the voltage
regulator terminal board regardless of any other optional modules in use!
†
Refer to your instructions that came with your Universal Voltage Regulator for the
interconnect diagrams to connect your voltage regulator to your generator.
White Red
Gray
XR or UVR series Universal Voltage Regulator †
AFM500X