Determining Which Hookup Configuration to Use
STOP!
This manual
ONLY
covers installation of the AFM500X
Automatic Flashing Module! If you are using an optional Static
Exciter Module, the installation of this product does not differ! Refer
to the instructions that came with your optional modules for their
correct wiring hookup.
The AFM500X is configurable for 2 different modes of operation:
Automatic Flashing
, and
Battery Flashing
.
YOU MUST CHOOSE ONE FLASHING METHOD OR THE OTHER!!
NEVER COMBINE THE TWO FLASHING METHODS! SEVERE
DAMAGE WILL RESULT!!!
To determine the proper connection for your generator you need to know the residual
AC voltage of your generator and which type of generator you have.
To determine the residual AC voltage of your generator, run engine with the
voltage regulator turned off and measure the voltage produced at the AC input
terminals of the voltage regulator then refer to the selection chart below:
When you have determined your residual AC voltage, select a Mode
(Automatic or Battery Flash) from the chart below:
•
Residual AC voltage is 2VAC or greater, or the generator has only occasional
problems building up voltage.
Use
Automatic Flash
(See Page 7)
•
Residual AC voltage is below 2VAC, the generator is a slip ring and brush
type, or guaranteed buildup is required.
Use
Battery Flash
(See Page 8)