SD700SP
POWER ELECTRONICS
14
TECHNICAL CHARACTERISTICS
TECHNICAL CHARACTERISTICS
The following table is for a standard SD700SP. Consult the technical brochure or Power Electronics for
further information.
INPUT
Power range
1,5kw - 560kw
[1]
Voltage power
380-500vac, 3 phases (±10%) 540-900vdc (830vdc for Frame 1 & 2)
Hybrid supply
Yes, simultaneous connection
Input frequency
50hz/60Hz ± 6%
Input rectifier technology
Thyristor-diode
DPF=cos phi / Power factor
≥ 0.98 / ≥ 0.91
EMC input filter
Frames 1 & 2: First environment (C2 Standard); Frames 3 to 8: second
environment (Industrial) (C3 Standard); first environment (C2 Optional).
C1 consult Power Electronics. Optional IT filter.
Current THDI (%) / Filter
harmonics
≤ 40% /
Choke coils 3% impedance
Regenerative
No
OUTPUT
Output frequency
[2]
0...200hz
Overload capacity
Constant torque/heavy duty: 150% during 60 sec at 50°c
Efficiency @rated current and
voltage)
≥ 98%
Switching frequency
4 to 8kHz - PEWave
Output dv/dt filter
500 to 800V/ms
[3]
Output cable length
[4]
USC 300m, SC 150m
ENIRONMENTAL
CONDITIONS
Operation temp. / storage temp.
-20°C to +50°C / -40°C to +70°C
Altitude/power altitude derating
[1]
1000m / >1000m, 1% Pn(kW) per 100m; 4000m maximum
Ambient humidity
<95%, non-condensing
Degree of protection
IP20, IP54
INPUTS / OUTPUTS
Digital inputs
6 Programmable active high (24vdc), Isolated power supply, 1 PTC input
Digital outputs
3 Programmable changeover relays (250vac, 8a or 30Vdc, 8a)
Analogue input
2 Programmable differential inputs: 0 - 20ma, 4 - 20ma, 0 - 10Vdc and
±10Vdc. (optically isolated)
Analogue outputs
2 Isolated programmable outputs: 0 - 20ma, 4 - 20ma, 0 - 10Vdc and
±10Vdc
Encoder inputs (optional)
2 Differential encoders input. voltages inputs from 5 to 24Vdc
User power supply
+24Vdc user power supply (max. 180mA) regulated and short-circuit
protected.
+10Vdc user power supply (max. 2 potentiometers r= 1 k
Ω
) regulated
and short-circuit protected
I/O Extension board (optional)
4 Digital Inputs: Programmable inputs and active high (24Vdc). optically
isolated.
1 Analogue Input: Programmable and differential input.
5 Digital Outputs: Programmable multi-function relays.
1 Analogue Output: Programmable outputs in voltage / current.
External power supply (optional)
24V External Power Supply, Fault Relay integrated
COMMUNICATION
Standard protocol
Modbus-RTU
Optional protocol
Profibus-DP, Devicenet, Ethernet (Modbus TCP), Ethernet IP, CAN open,
N2 Metasys Gateway
OUTPUT
Certifications
CE, cTick, UL
[5]
, CUL
[5]
, GL
[6]
Electromagnetic compatibility
EMC directive (2004/108/CE), IEC/EN 61800-3
Design and construction
LVD directive (2006/95/CE), IEC/EN 61800-2, IEC/EN 61800-5-1, IEC/EN
60146-1-1, IEC60068-2-6, IEC/EN 61800-5-2(sto) TÜV Rheinland
Certified
[1] For other configuration, consult Power Electronics.
[2] For operation frequencies higher than 100Hz, consult Power Electronics.
[3] Valid for frames 3 to 8, depending on the rated power, the input voltage and under Power Electronics' installation recommendations. For
Frames 1 and 2, optional filters are available.
[4] SC: Shielded cable, USC: Unshielded Cable. Follow Power Electronics installation recommendations. For greater cable lengths and first
environment (C2) consult Power Electronics.
[5] On certification process.
[6] SD700 series from frame 5 on.
3
Summary of Contents for SD700SP Series
Page 2: ......
Page 42: ...SD700SP POWER ELECTRONICS 40 POWER CONNECTION Connections for Frame 3 Connections for Frame 4...
Page 43: ...POWER ELECTRONICS SD700SP POWER CONNECTION 41 EN Connections for Frame 5...
Page 44: ...SD700SP POWER ELECTRONICS 42 POWER CONNECTION Connections for Frame 6...
Page 45: ...POWER ELECTRONICS SD700SP POWER CONNECTION 43 EN Connections for Frame 7...
Page 46: ...SD700SP POWER ELECTRONICS 44 POWER CONNECTION Connections for Frame 8...