SD700SP
POWER ELECTRONICS
54
MAINTENANCE
MAINTENANCE
SD700SP drives consist of advanced semiconductor devices. Temperature, humidity, vibration and
deteriorated components can reduce their efficiency. To avoid any possible irregularity, we recommend
making periodic inspections.
Warnings
•
Make sure to remove the input power while performing maintenance.
•
Make sure to perform maintenance after checking the DC Link capacitor has discharged. Check
that the voltage between terHVDC and -HVDC is below DC 30V. The bus capacitors in
the drive main circuit can still be charged even after the power is turned off.
•
The correct output voltage of the drive can only be measured by using an RMS voltage meter.
Others voltage meters, including digital voltage meters, are likely to display incorrect values caused
by the high frequency PWM output voltage of the drive.
Routine Inspection
Make sure to check the following points before handling the drive:
•
Installation site conditions.
•
Drive cooling system conditions.
•
Excessive vibrations or noise in the motor.
•
Excessive overheating.
•
Normal output current value on the monitor.
In
sp
ec
tio
n
si
te
Inspection
element
Inspection
Period
Inspection method
Criterion
Instrument of
Measurement
M
on
th
ly
1
ye
ar
2
ye
ar
s
All
Ambient
conditions
Are there dust particles?
Are the ambient
temperature and the
humidity within
specification?
o
Visual check
Temperature:
-30 to +50 ( or 40ºC)
Humidity: below 95% non-
condensing.
Thermometer,
Hygrometer,
Recorder.
Module
Are there any abnormal
noises or oscillations?
o
Visual and audible.
There are no anomalies.
Input power
Is the input power to the
main circuit correct?
o
Measure the voltage between
terminals L1, L2, L3 and PE.
Measure the voltage between
terminals VDC+, VDC- and
check it is compatible with the
drive DC voltage range .
Digital
multimeter.
Tester.
Power
connections
Are the Power terminals
correctly fastened?
o
Measure the temperature and
torque of the power
connections
Fasten the bolts again one
week after its start-up.
Check that the
temperature is
homogeneous and below
70ºC
Infrared
thermometer ,
Torque key
12
Summary of Contents for SD700SP Series
Page 2: ......
Page 42: ...SD700SP POWER ELECTRONICS 40 POWER CONNECTION Connections for Frame 3 Connections for Frame 4...
Page 43: ...POWER ELECTRONICS SD700SP POWER CONNECTION 41 EN Connections for Frame 5...
Page 44: ...SD700SP POWER ELECTRONICS 42 POWER CONNECTION Connections for Frame 6...
Page 45: ...POWER ELECTRONICS SD700SP POWER CONNECTION 43 EN Connections for Frame 7...
Page 46: ...SD700SP POWER ELECTRONICS 44 POWER CONNECTION Connections for Frame 8...