Powered by Safety
®
8
Equipment Description
EcoVisor™
01.4IB.48080
c. S
pecificAtionS
Table A System Sensor Specifications
Parameter
Detection
Range
Accuracy
Resolution
Refresh
Rate
Response
Time*
Sensors
Dust
0-1 mm
±0.05 mm
0.01 mm
50 ms
15s
Relative Humidity
20% to 95% RH
See
0.1% RH
1s
90s
Temperature
-40
°
C to +85
°
C
±1.5
°
C
0.1
°
C
1s
9min
Physical
Approximate Dimensions
3.25” x 3.75” max
Enclosure Material
Injection molded PC/ABS blend (UL 94 V-0 rated)
Mounting
2 x 1/4” (6.25mm) holes on 3.9” (99mm) center, see
Ch 4 Installation, A. Mounting
for details
Interface
1 button
Power Requirements
Voltage Range
10 - 24 VDC
Max Current
0.1A
Max Power
1W
Environmental Operating Conditions
Operating Temperature &
Storage Temperature
-40
°
C to 85
°
C
Humidity
20% - 95%RH
Communication Interface
Interface to BriteSpot
®
Plus
RS-485
Standalone Modbus
RS-485
Supported Baud Rates
9600, 19200, 38400, 57600, 115200
Maximum Polling Rate
1 Modbus RTU request per second
Indicators
COM LED
Bi-color LED for indication of communication status - see
Table B, EcoVisor™ LED Indicators
for
definitions
HEALTH LED
Bi-color LED for indication of power and environmental conditions - see
for definitions