Operation
EcoVisor™
01.4IB.48080
B. o
perAtion
WitH
B
rite
S
pot
® p
luS
1) Electrical Connection
For connection to the BriteSpot Plus, a
6p6c modular cable must be terminated to
match the client port pinout described in
the BriteSpot Plus instruction bulletin and
connections made as directed.
2) Setup
Refer to the most recent version of the
BriteSpot Plus instruction bulletin for
information on Web Interface to set up the
EcoVisor
™
connection.
c. Q
uick
S
tArt
G
uide
1) Establishing Connection to the EcoVisor
Note:
This procedure assumes that the
EcoVisor is in its default state. Should
it be necessary to return to this state
refer to
a. Download and install Modbus Poll:
http://www.modbustools.com/download.
.
b. Power EcoVisor with 10 – 30VDC.
c. Connect the EcoVisor to a computer
using a suitable RS-485 converter, see
connection diagram in
.
Figure 9
Connection Diagram
Ec o V i s o r ™ LO O K I N G I N TO CO N N EC TO R
1 - G N D
2 - N C
3 - N C
4 - RS - 4 8 5 B
5 - RS - 4 8 5 A
6 - + V
I N
6 5 4 3 2 1 6 5 4 3 2 1
DC 10V - 24V
+
-
RS-485
CONVERTOR
A
B
USB
COMPUTER
d. Use the Modbus RTU communication
tool and the information provided in
configure communication with the
EcoVisor.
e. Set up connection as shown in
(select the appropriate COM
port and other settings in the “serial
settings” panel of the software).
Figure 10 Initial Connection Setup