Installation
120
-393 632
.4 04.08 F
h
PARAMOUNT two 30 - 115 kW
29
International protection IPx4D
The screwed cable connections have to be tightened in order to
meet international protection IPx4D and the specified air-tight
sealing of the air chamber, so that the seal rings seal the cables.
Circulating pumps
The permissible current load per pump is I
N max
= 1A.
Fuses
Fuses in the Control Unit:
- F1 - T 6,3 H 250 ; mains
Connecting sensors/ components
Danger of electric shock! Observe wiring diagram!
Assemble and connect accessories according to enclosed instruc-
tions. Check earthing.
Outdoor temperature sensor (included with boilor)
The outside temperature sensor is enclosed in the enclosed pa-
ckage. For connection see wiring diagram.
Replacing cables
All connecting cables, except for the mains connection cable, have
to be replaced by POTTERON Commercial-special cables in case of
replacement. When replacing the mains connection cable, only ca-
bles of the types H05VV-F can be used, complying with BS 6500.
Contact protection and international protection IPx4D
To ensure contact protection and international protection IPx4d,
the covering parts to be screwed, have to be fastened again with
the respective screws after opening the PARAMOUNT two.
Fig. 8: Strain relief
1.
Insert cables and snap shut clips until they lock
2.
Press down clip screws
3.
Tighten clip screw with screw driver
4.
Lever open the snap-mechanism with a screw driver to open the cable clips
1
2
3
4