Programming
120
-393 632
.4 04.08 F
h
PARAMOUNT two 30 - 115 kW
55
te switch). The modem function is activated when the contact is
closed.
Modem inverse: The modem function is activated when the con-
tact is opened.
Warm air curtain function: With this funtion the programmable
output is activated, when the input for the warm air curtain func-
tion has been set. If this input has not been set, also the output
will be set back. The warm air curtain funtion allows the maximum
nominal boiler temperature to be achieved. Also, a heat request is
set for heating circuit 1.
Check sign flue gas damper: Checkback via input H1 in case of ac-
tivated flue gas damper control.
Heat generation lock: The heat generation lock is needed to lock
the burner in case of integrating alternative energies (e.g. solar
energy). The heat generation lock is activated, when the contact
is closed (see also prog. no. 2201, prog. no. 6330, and program-
ming manual)
Heat generation lock inverse: The heat generation lock is activa-
ted, when the contact is opened.
Modem function
(5957)
Optg mode change HCs+DHW: Changing over of the operating mode
for heating circuit and DHW via telephone remote switch.
Optg mode changeover HC 1/2: Changing over of the operating
mode for heating circuit 1/2 via telephone remote switch.
Configuration room
thermostat 1/2
(5970, 5971)
None: Switching the input has no effect.
Room themostat: the switching status of the contact decides, if a
heat request has to be generated.
It applies:
Input open: Heat request locked
Input closed: Heat request released
If no room thermostat is connected, the heat request remains lo-
cked.
Timer room level: This function switches over the room setpoint.
It applies:
Input open: Room setpoint = Reduced setpoint
Input closed: Room setpoint = Comfort setpoint
Time switch heat request: See function Room thermostat.
Time switch DHW level: This function switches over the DHW set-
point.
It applies:
Input open: DHW setpoint = Reduced setpoint
Input closed: DHW setpoint = Nominal setpoint
Function input relay
clip-in
(5973)
None: No function.
Modem: See prog. no. 5950.
Modem inverse: See prog. no. 5950.
Warm air curtain function: See prog no. 5920.
Specified setpoints (heat request:) The existing voltage signal or
current signal will be converted into a temperature value and used