26
12.0 Fault Finding
Is there a spark at the
electrode?
NO
Check and clean the
spark electrode
Check condition of spark
lead and connection at
burner ignition control
Replace pilot assembly if
lead is damaged
Check the spark gap is
3.0 ±0.5mm
Is the Boiler Safety
Overheat neon illuminated?
Unscrew the cover and
press the reset button
YES
If sparking does not start
is there 230V at L & N
connections on the Boiler
Safety Overheat neon ?
Replace the neon
YES
Is there continuity across
Safety Overheat
Thermostat connections
W28 & W29?
NO
NO
Is there continuity across
Temperature Control
Thermostat connections
W20 & W21?
YES
Is there continuity across
Flue Safety Thermostat at
connections T & H on
terminal strip?
YES
NO
NO
YES
Does the pump run ?
NO
Is there 230V at PL & PN
on the terminal strip?
YES
Check pump or pump
wiring
Check boiler internal
wiring
NO
YES
Replace pump
NO
Check flue for blockage or
adverse conditions
Check continuity of wiring
Replace Flue Safety
Thermostat
Check boiler flow temperature
Check continuity of wiring
Replace Temperature
Control Thermostat
If boiler overheated
establish cause
Check continuity of wiring
Replace Safety
Overheat Thermostat