iHE
15
Concentric Flue
Conventional Flue
Item
F.E.L.
1m length
1.0
45° bend
0.5
90° bend
1.0
Horizontal Terminal
1.0
Vertical Terminal
1.6
Flue
Parts
Part
Number
1.0 m Concentric Length
E212
0.5m Concentric Length
E214
Concentric 90° Bend
E215
Concentric 45° Bend
E216
Flue Condense Trap
E220
Horizontal Terminal kit
E240
Terminal
Guard
E630
Vertical Terminal kit
E670
Wall Clamp 200mm
E219
Flue
Parts
Part
Number
Flue Clamp, 130 mm
TBC
Angle Roof Plate
TBC
Flat Roof Plate
TBC
1m x 130mm Flue Length
TBC
130mm 90° Elbow
TBC
130mm 45° Elbow
TBC
Debris
Guard
TBC
Item
F.E.L.
NB Do not include the Twin Adapter
1m length
1.0
45° bend
0.5
90° bend
1.0
Horizontal Terminal
1.0
Vertical Terminal
1.6
Examples:
Concentric Flue Type C
13
A
fl
ue system that uses ten straight lengths, three
90° bends, two 45
o
bends and a horizontal termi-
nal.
10 x 1m straight length
10.0
3 x 90° bends
3.0
2 x 45
o
bends
1.0
1 x Horizontal Terminal
1.0
Total
(within 18m limit)
15.0
Concentric Flue Type C
33
A system that rises from the Heater and uses
seven straight lengths, four 45° bends and a verti-
cal terminal.
7 x 1m straight lengths
7.0
4 x 45° bends
2.0
Vertical
Terminal 1.6
Total
(within 18m limit)
10.6
Open Flue Type B
23
The maximum
FEL
of
fl
ue in this con
fi
guration is
25 metres.
The air inlet connection to the appliance must
be
fi
tted with a Debris Guard. Air is drawn from
the room or compartment in which the heater is
installed and therefore the room or compartment
must be ventilated.
See Page 11.
The
fl
ue duct can discharge either vertically or hori-
zontally by selection of the correct
fl
ue terminal.
The
fl
ue pipe can be
fi
tted with 90 and 45 degree
bends as well as extensions.
Example:
A
B
23
system with air collected from the plant room
and the
fl
ue exiting via twelve straight lengths and
four 45° bends to a roof terminal.
4 x 1 m straight lengths of FLUE. 12.0
4 x 45° bends of FLUE
2.0
1 x Roof Terminal
1.6
Total
(within 30m limit)
15.6
Summary of Contents for iHE 100/300
Page 1: ...M6500 M6500 ...
Page 21: ...iHE 19 Fig 4 3 WIRING DIAGRAM PCB 1 ...
Page 22: ...iHE 20 WIRING DIAGRAM PCB 2 3 Fig 4 4 ...
Page 34: ...iHE 32 APPLIANCE COMPONENTS Fig 7 1 21 20 17 22 19 18 16 24 25 26 27 28 29 23 ...
Page 39: ...NOTES ...
Page 40: ...Publication Date 01 09 12 ...