iHE
35
Table 3.0
10
Outside sensor, error
Check connections and / or replace faulty sensor
(B9)
20
Boiler temperature 1, sensor error
Check connections and / or replace faulty sensor (B2)
26 Common
fl
ow temperature, sensor error
Check connections and / or replace faulty sensor (B10)
28
Flue gas temperature, sensor error
Check connections and / or replace faulty sensor (B8)
30
Flow temperature 1, sensor error
Check connections and / or replace faulty sensor (B1)
32
Flow temperature 2, sensor error
Check connections and / or replace faulty sensor (B12)
40
Return temperature 1, sensor error
Check connections and / or replace faulty sensor (B7)
50
DHW temperature 1, sensor error
Check connections and / or replace faulty sensor (B3)
60
Room temperature 1, sensor error
Check connections and / or replace faulty sensor (R1)
65
Room temperature 2, sensor error
Check connections and / or replace faulty sensor (R2)
68
Room temperature 3, sensor error
Check connections and / or replace faulty sensor (R3)
70
Stoarge tank temperature 1, sensor error
Check connections and / or replace faulty sensor (B4)
83
LPB collision
Duplicate LPB address - Check all PCBs function 6600
84
BSB address collision
Room unit incorrectly con
fi
gured - see function 40
98
Extension module 1, error
Module 1 con
fi
guration error - Check parameters
99
Extension module 2, error
Module 2 con
fi
guration error - Check parameters
100
2 Clock time masters
Only PCB no 1 is set as time master - see Function 6640
110
STB lockout
Check connector X18a and all
fl
ow & return sensors
111
Shutdown limit thermostat
Heat exchanger temperatures have been exceeded
121
Flow temperature heating circuit 1 not reached
Htg Circuit 1, time temp parameter not reached
122
Flow temperature heating circuit 2 not reached
Htg Circuit 2, time temp parameter not reached
126
DHW charging temperature not reached
Check operation and heat up times for DHW
127
DHW legionella temperature not reached
Check operation of appliance
128 Loss
of
fl
ame during operation
Ionisation current lost after successful ignition
130
Flue gas temp too high
Heat Engine is overheating. Check causes of high temps
133
Safety time exceeded
Ignition unsuccessful after 5 attempts
151
BMU Internal error
Check polarity is not reversed to the appliance
152
Parameterization
error
Incorrect
/
Con
fl
icting parameters input.
FAULT CODES
Code Fault Description
Notes
Summary of Contents for iHE 100/300
Page 1: ...M6500 M6500 ...
Page 21: ...iHE 19 Fig 4 3 WIRING DIAGRAM PCB 1 ...
Page 22: ...iHE 20 WIRING DIAGRAM PCB 2 3 Fig 4 4 ...
Page 34: ...iHE 32 APPLIANCE COMPONENTS Fig 7 1 21 20 17 22 19 18 16 24 25 26 27 28 29 23 ...
Page 39: ...NOTES ...
Page 40: ...Publication Date 01 09 12 ...