70
Figure 8.2
– Over-pressure valve
Position of the valve
LEGEND
Detail of the refrigerant fl exible ducting pipe
8.3
ADDITIONAL SAFETY DEVICES
The following additional safety devices are installed on the appliance:
•
Generator limit thermostat (see pos. A in the Figure 8.1 on page 69).
•
By-pass valve (see pos. B in the Figure 8.1 on page 69).
The main features of the two devices are given in Table 8.3 on page 70.
Table 8.3
– Characteristics of the two devices
TYPE
CALIBRATION
MODEL
PRODUCT CODE
GENERATOR
LIMIT THERMOSTAT
Thermostat single pole disc
Bimetallic manual reset and
rapid opening of the contact .
Contact N.C. (normaly closed)
180° C ± 7° C
CAMPINI COREL
code
60R180H02/04154
or similar*
J-TLT015
BY-PASS VALVE
Mechanical stopper valve
25,5 +0/-2 bar
Potterton.
code
H-VLV105
---
* The manufacturer guarantees the safety of operation and only when equipped with original spare parts
In the case of replacement, the use of original spare parts is recommended (see codes
in Table 8.3). The manufacturer is exempt from any contractual or extra-contractual
responsibility for damage caused by the use of non-original spare parts.
INSPECTION PROCEDURE
Before starting the inspection of the generator limit thermostat, the unit must be isolated
from the electrical supply and gas supply after which the unit can be worked on as
follows:
1. Move the appliance front panel;
2. Identify the thermostat, which is found in the lower part of the generator pipe,
on the right side above the combustion chamber (see fi gure 8.3 Inspection at
generator limit thermostati on page 71);
3. Disconnect the cables (see Figure 8.3 Inspection at generator limit thermostati on
page 71);
4.
Inspect or replace the component (to disassemble the component, turn it
anti-clockwise);