Installation, user and maintenance manual
– GAHP-A
67
8
APPENDIX
8.1
MACHINE OPERATING CODES
Table 8.1
– TABLE OF OPERATING CODES generated by S61 controller (fi rmware version 3.016)
CODES
DESCRIPTION
TRIP CONDITIONS
RESET METHOD
E 400
FAULT ON RESET CIRCUIT OF FLAME
CONTROL UNIT
Fault on reset circuit of fl ame control unit.
Contact authorised Potterton TAC.
u 401
GENERATOR LIMIT TEMPERATURE
THERMOSTAT
High temperature detected by limit thermostat
on body of generator
Reset limit thermostat manually: operation will be restored
automatically when the cause ceases.
E 401
GENERATOR LIMIT TEMPERATURE
THERMOSTAT
u_01 code active for 1 hour, or u_01 code
generated 3 times in 2 hours of operation.
Contact authorised Potterton TAC.
u 402
FUMES THERMOSTAT
High temperature detected by exhaust fumes
thermostat
Reset occurs automatically when the condition that generated the
code ceases.
E 402
FUMES THERMOSTAT
u_02 code active for 1 hour, or u_02 code
generated 3 times in 2 hours of operation.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If codes u_02 and/or E_02 occur again,
contact authorised Potterton TAC.
E 405
HIGH AMBIENT TEMPERATURE
HIGH temperature detected by ambient
temperature sensor.
Reset occurs automatically when the condition that generated the
code ceases.
E 406
LOW AMBIENT TEMPERATURE
LOW temperature detected by ambient
temperature sensor.
Reset occurs automatically when the condition that generated the
code ceases.
u 407
HIGH CONDENSER INLET
TEMPERATURE
HIGH temperature detected by condenser inlet
temperature sensor or fumes sensor.
Reset occurs automatically when the condition that generated the
code ceases.
E 407
HIGH CONDENSER INLET
TEMPERATURE
u_07 code active for 1 hour, or u_07 code
generated 12 times in 2 hours of operation.
Carry out appropriate checks. Reset may be performed from the
CCI/DDC (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Potterton TAC.
E 408
FLAME CONTROL UNIT ERROR
E_12 on unit and condenser inlet temperature
increasing by over 10 °C within 1 hour.
Carry out appropriate checks. Reset may be performed from the
CCI/DDC (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Potterton TAC.
u 410
INSUFFICIENT HOT WATER FLOW
Insuffi cient water fl ow (the circulator is on and
the fl owmeter measure a low water fl ow).
Reset occurs automatically when correct water fl ow is restored.
E 410
INSUFFICIENT HOT WATER FLOW
u_10 code is repeated, or code u_10 is active for
1 hour.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
u 411
INSUFFICIENT ROTATION OF OIL
PRESSURE PUMP
Insuffi cient rotation of oil pressure pump.
Reset occurs automatically 20 minutes after the Code is generated.
E 411
INSUFFICIENT ROTATION OF OIL
PRESSURE PUMP
u_11 code generated twice in 2 hours of
operation.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
u 412
FLAME CONTROL UNIT ARREST
Failure to ignite burner.
Reset occurs automatically when the solenoid valve opens again
(new ignition attempt), or if the code persists for 5 minutes.
E 412
FLAME CONTROL UNIT ARREST
Flame arrest signal.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 20). If the code persists, contact authorised
Potterton TAC.
E 416
HOT OUTLET WATER TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on hot outlet
water temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
E 417
COLD INLET WATER TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on inlet water
temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
E 420
CONDENSER INLET TEMPERATURE
SENSOR DEFECTIVE
Fault (interruption or short circuit) on condenser
inlet temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
E 422
WATER FLOWMETER FAULT
Water fl owmeter fault
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
E 423
AIR/GAS MIXTURE SENSOR FAULT
Air gas mixture sensor fault
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
E 424
FUMES TEMPERATURE SENSOR
FAULT
Fumes temperature sensor fault
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
E 428
GAS SOLENOID VALVE EXCITED
DURING FLAME CONTROLLER
ARREST
The fl ame controller is arrested (E_12) but the gas
solenoid valve is excited. In this case the fl ame
controller is de-excited (E_12 resets).
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
u 429
GAS SOLENOID VALVE WITHOUT
ELECTRICAL POWER
Gas solenoid valve is off for 5 seconds (with
central fl ame control unit on).
Reset occurs automatically if the gas solenoid valve switches on
again within 10 minutes (with central fl ame control unit on).
E 429
GAS SOLENOID VALVE WITHOUT
ELECTRICAL POWER
Code u_29 is active for more than 10 minutes
(with fl ame controller unit on).
Carry out appropriate checks. Reset may be performed from the
CCI/DDC (or from the S61 board via menu 2, parameter 21). If the
code persists, contact authorised Potterton TAC.
E 436
BLOWER FAULT
Blower fault
Reset may be performed from the CCI/DDC (or from the S61 board
via menu 2, parameter 21). If the code persists, contact authorised
Potterton TAC.
E 437
LOW COMBURENT AIR
TEMPERATURE
Air comburent temperature equal or smaller of
-10 °C
Reset occurs automatically when the condition that generated the
code ceases.