background image

1. Description

This document provides instructions for mounting and wiring the detector bases 

PAD100-LFSB and PAD100-SPKB.  The following detectors are compatible with 

detector bases PAD100-LFSB and PAD100-SPKB.

  PAD100-PD: 

Photoelectric Smoke Detector

  PAD100-PHD: 

Photoelectric Smoke / Heat Detector

  PAD100-HD: 

Heat Detector

  PAD100-CD: 

Carbon Monoxide Detector

2a. Field Wiring Diagram for PAD100-LFSB

Typical field wiring diagrams for the Signaling Line Circuit (SLC) (FIGURE 1).  The 

SLC supports NFPA wiring Class B, A and X.  (FIGURE 1) Typical of NFPA Class B SLC 

(S+, S-) Wiring using the PAD100-LFSB base.  In Class A arrangement two separate 

conductors would return from the last detector base to a listed compatible Fire 

Alarm Control Panel (FACP).  

Class X Wiring (FIGURE 2), requires use of PAD100-IM (Addressable Isolator 

Module).  The typical field diagram is in Field Wiring Diagram(s) for PAD100-IM.  

The PAD100-IM manual can be obtained at www.pottersignal.com

2b. Field Wiring Diagram for PAD100-SPKB

Typical field wiring diagrams for the Signaling Line Circuit (SLC) (FIGURE 4).  The 

SLC supports NFPA wiring Class B, A and X.  The PAD100-SPKB offer a choice of 

field selectable power taps: 1/8, 1/4, 1/2, 1, 2 and 4 watts (FIGURE 5) for use 

with either 25 VRMs or 70.7 VRMs audio amplifiers.  The frequency range of the 

PAD100-SPKB is 400-4000 Hz.  The PAD100-SPKB is suitable for line supervision.  

The PAD100-SPKB includes DC blocking capacitor which allows for supervision 

voltage of either polarity.

3. Wiring Instruction

  To ensure proper installation of the detector head to the base, wires shall be 

  dressed properly at the time of installation

  When using PAD100-SPKB / PAD100-LFSB base, observe the correct polarity of 

  SLC wiring.

NOTICE:

 

 

THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE 

  PROVISIONS OF ARTICLE 300.3(B) OF THE NATIONAL ELECTRICAL CODE, 

  NFPA 70, AS WELL AS ARTICLE 210.

  THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE 

  NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 72.

  DO NOT USE LOOPED WIRE UNDER TERMINALS.  BREAK WIRE RUN TO 

  PROVIDE SUPERVISION OF CONNECTION.

CAUTION!

 

 

Break wire runs to provide supervision for connections made to each wire pair.

 

When installing, route field wiring away from sharp projections, corners and 

  internal components.

Detector Base Mounting

PAD100-LFSB / PAD100-SPKB should be mounted directly on the electrical box 

(FIGURE 6a) or to the LFSBBB-W back box (FIGURE 6b).  The PAD100-LFSB / 

PAD100-SPKB mounting holes are configured for a 4” x 2-1/8” deep square box.    

Use a box for each base and run the power circuit to all base locations.  
Use 12 to 18 AWG conductors to connect to terminals of bases.  It is 

recommended that the SLC conductors be color-coded to avoid wiring errors and 

assist in system troubleshooting.  Improper SLC connections may prevent the 

system from operating normally.  Disconnect power to the SLC until the detectors 

are installed.

1.  Wire the detector bases according to Field Wiring Diagrams.

2.  Use the dip switches (SECTION 11) to set address(es) (1 - 127) for each 

  detector head.  

NOTICE: 

 

THE PAD100-LFSB /PAD100-SPKB OBTAINS THE ADDRESS FROM THE 

  DETECTOR HEAD.

 

THE DETECTORS AND THE PAD100 MODULES MUST HAVE INDIVIDUAL 

  ADDRESS(ES).

3.  To install the detector head onto the base, match the detector heads to the 

  base using the alignment feature and twist clockwise until the detector heads 

  snap into place (FIGURE 6a).

Installation Manual 

Detector Bases: 

PAD100-LFSB, PAD100-SPKB

PAD100-PD 

 

Photoelectric Smoke Detector  

 

 

(ANSI/UL 268 Listed)

PAD100-PHD 

 

Photoelectric Smoke / Heat Detector Combination  (ANSI/UL 268 and ANSI/UL 521 Listed)

PAD100-HD 

 

Heat Detector    

 

 

 

(ANSI/UL 521 Listed)

PAD100-CD 

 

Carbon Monoxide Detector  

 

 

(ANSI/UL 2075 Listed)

FIGURE 4: 

PAD100-SPKB Wiring Diagram 

SPK

SLC

FIGURE 5: 

PAD100-SPKB Wiring and Power Tap

Adjust power taps using 

needle nose pliers.

 SLC -

To FACP

Loop (SLC)

First Base

- PWR +

S +

S -

S +

S -

24+

24-

SLC +

 SLC -

- PWR +

SLC +

Last Base

FIGURE 1: 

Wiring (Class B) Using PAD100-LFSB

PWR

SLC

FIGURE 3: 

PAD100-LFSB Wiring

FIGURE 2: 

Wiring (Class X) Using PAD100-LFSB and PAD100-IM 

FACP

IM

ISOLATOR MODULE

THE IM NEXT TO A FACP SHALL BE INSTALLED

WITHIN 20 FEET FROM THE TERMINAL OF THE FACP

SHORT CIRCUIT

THE AREA TO BE ISOLATED BY 

DETECTING THE SHORT CIRCUIT

IM

IM

IM

SLC

OUT

SLC

IN

Manual Number: 550-0706

Summary of Contents for PAD100-LFSB

Page 1: ...K WIRE RUN TO PROVIDE SUPERVISION OF CONNECTION CAUTION Break wire runs to provide supervision for connections made to each wire pair When installing route field wiring away from sharp projections corners and internal components Detector Base Mounting PAD100 LFSB PAD100 SPKB should be mounted directly on the electrical box FIGURE 6a or to the LFSBBB W back box FIGURE 6b The PAD100 LFSB PAD100 SPKB...

Page 2: ...e Safeguard Model 25S or SDi Smoke Centurion as acceptable to the Authority Having Jurisdiction AHJ b PAD100 PHD and PAD100 HD Heat Detectors NOTICE TAKE CARE DURING THE HEATING OF THE DETECTOR TO AVOID OVERHEATING THE PLASTIC HOUSING Use of a low powered heat gun is acceptable CAUTION Do not heat over 210o F 98 9o C Maintain a minimum of 1 foot between the detector and the heat gun nozzle Heat th...

Page 3: ...hat locks the detector and does not allow removal without the use of a tool 1 Once the detector has been installed the detector locks into the base To remove the detector from the base insert a small screwdriver into the slot on the detector FIGURE 11 and push the plastic tab while simultaneously turning the detector head counter clockwise 2 The locking feature can be disabled To disable the locki...

Page 4: ...tandby Current 300 µA 3 Alarm Indicator 1 LED 4 Alarm Indictor Current 1 4 mA 5 Alarm Set Point Range 1 0 3 7 ft 3 6 12 m 1 0 3 7 ft 3 6 12 m 135O to 174O F 57O to 79O C 135O to 174O F 57O to 79O C 175O to 185O F 80O to 85O C 135O to 160O F 57O to 71O C Fixed 70 150 400 PPM 6 Installation Temperature Range 32O to 120O F 0O to 49O C 32O to 115O F 0O to 46O C 32O to 100O F 0O to 38O C 32O to 150O F ...

Page 5: ...ce either amplifier input or gain PAD100 SPKB Field Selectable Power Tap Selection Reverberant dBA 10ft Voltage 1 8 Watt 1 4 Watt 1 2 Watt 1 Watt 2 Watt 4 Watt 25 Volts 75 0 dBA 78 1 dBA 81 2 dBA 83 8 dBA 86 6 dBA 89 7 dBA 70 7 Volts 75 1 dBA 78 1 dBA 80 9 dBA 83 8 dBA 86 9 dBA 89 6 dBA 11 PAD Protocol Dip Switch Settings The following information is for setting the dipswitches on the PAD100 PD PA...

Page 6: ...er Electric Signal Company LLC personnel at Potter Electric Signal Company LLC s facilities in Hazelwood Missouri You must also pack the appliance to minimize the risk of it being damaged in transit If we receive an appliance in a damaged condition as the result of shipping we will notify you and you must seek a claim with the shipper If you submit a valid claim to Potter Electric Signal Company L...

Reviews: