background image

4.  After all detector heads, addressable bases and modules have been 

  installed, apply power to the FACP.

5.  Test the detectors as described in the Testing Section of this manual.

NOTICE:

  

DO NOT INSTALL DETECTOR HEADS UNTIL AREA HAS BEEN 

THOROUGHLY CLEANED TO REMOVE CONSTRUCTION DEBRIS, DUST, ETC., 

AS REQUIRED BY NFPA 72. 

 

4.  Spacing Limitations

NOTICE: 

REFER TO NFPA 72 FOR SPECIFIC INFORMATION REGARDING DETECTOR 

SPACING, MOUNTING LOCATION AND SPECIAL APPLICATIONS.

PAD100-PD, PAD100-PHD: Photoelectric Smoke Detector

PAD100-PD and PAD100-PHD are ANSI/UL listed on maximum 30ft spacing 

limitation with alarm set point from 135

O

-174

F on smooth ceiling.  Refer to 

NFPA 72 for specific information regarding detector spacing, placement and 

special applications.  

PAD100-HD: Heat Detector

The ANSI/UL listed spacing limitations of PAD100-HD smooth ceiling are 

dependent on alarm set point.

5. Testing

Testing shall be performed periodically to determine if each detector operates 

properly.  Detectors will offer maximum performance when tested in compliance 

with NFPA 72.

NOTICE: 

REFER TO FIRE ALARM CONTROL PANEL (FACP) MANUAL FOR 

OPERATION OF DIRTY VALUE READ / PRINT, ALARM SIMULATION AND WALK 

TEST.

Operational Testing

When PAD100-PD, PAD100-PHD, PAD100-HD and  PAD100-CD are under normal 

conditions in standby mode, the alarm indicator LEDs will pulse approximately 

once every 4 seconds.

NOTICE:

 WHEN A PANEL IS CONFIGURED TO NOT FLASH LEDS, THE LEDS ON 

THE DETECTORS WILL NOT FLASH AT ANY TIME.

Sensitivity Testing

(Dirty Value Read / Print)

The sensitivity drift value (Dirty Value) of the smoke detector can be checked at 

the FACP.  The Dirty Value can be read and printed out at the FACP.  

NOTICE: 

DETECTOR COMPENSATES SENSITIVITY UNTIL LIMIT OF 

COMPENSATION.  WHEN COMPENSATION RATE REACHES LIMIT, A TROUBLE 

SIGNAL WILL BE INDICATED ON THE FACP.

Functional Testing

NOTICE:

 BE SURE TO DIS-ENGAGE ALL ALARM SIGNAL SERVICES, 

RELEASING DEVICES AND EXTINGUISHING SYSTEMS, PRIOR TO 

PERFORMING THE FOLLOWING TEST, EXCEPT AUTOMATIC TESTING BY 

THE FACP.  BE SURE TO RE-ENGAGE THESE SYSTEMS WHEN ALL TESTING IS 

COMPLETE.

Walk Test

The FACP must be placed into Walk Test Mode and follow the steps below.  Use 

the appropriate steps outlined below for the detector that is to be tested.  

CAUTION!

 FAILURE TO ALARM DURING A TEST INDICATES A DEFECTIVE 

DETECTOR.  REPLACE DETECTOR IMMEDIATELY.
a.  PAD100-PD and PAD100-PHD Smoke Detectors: Use a ANSI/UL listed aerosol 

  such as Home Safeguard Model 25S or SDi Smoke Centurion as acceptable to 

  the Authority Having Jurisdiction (AHJ).

b. PAD100-PHD and PAD100-HD Heat Detectors: 

NOTICE:

 TAKE CARE DURING THE HEATING OF THE DETECTOR TO AVOID 

OVERHEATING THE PLASTIC HOUSING.

   

Use of a low powered heat gun is acceptable. 

 

    CAUTION!

 Do not heat over 210

o

F (98.9

o

C). 

  

  Maintain a minimum of 1 foot between the detector and the heat gun 

    nozzle.

  

  Heat the detector for a minimum of 10 seconds.

  

  FACP will indicate with alarm when a sufficient amount of heat has been 

    applied.  LED indicator will continuously flash while detector is in alarm.  

c.  PAD100-CD: Carbon Monoxide Detectors: Use the Home Safeguard Model 

  HO-CO2 Aerosol with Home Safeguard Model Versa-Test Head VT1 or the SDI 

  Solo C6 Aerosol with SDI Solo 330 Dispenser as acceptable to the Authority  

  Having Jurisdiction (AHJ).

NOTICE:

 NEVER USE EXHAUST FROM VEHICLE TO TEST CO PORTION OF 

DETECTOR.  EXHAUST MAY CAUSE PERMANENT DAMAGE TO DETECTOR 

AND VOIDS THE WARRANTY.

6. Maintenance

The detector should be cleaned as needed.  Detectors installed in environments 

more prone to dust may need cleaning based on build-up of dust.  The Dirty 

Value Report provides an indication when the detectors should be cleaned.

NOTICE: 

  THE DETECTOR IS NOT WASHABLE, DO NOT SUBMERGE THE DETECTOR IN 

  WATER.  WATER CAN AFFECT THE SENSOR, CAUSING PERMANENT 

  DAMAGE.

  DO NOT SPRAY CLEANING CHEMICALS OR INSECT SPRAYS DIRECTLY ON 

  OR NEAR THE DETECTOR.  DO NOT PAINT OVER THE DETECTOR.  DOING 

  SO MAY CAUSE PERMANENT DAMAGE.
a.  PAD100-PHD, PAD100-HD and PAD100-CD: When cleaning is needed, clean 

  cover using a soft cloth.  

 

 

DO NOT vacuum or use compressed air, water, cleaners or solvents to clean 

    the detector.

 

 

DO NOT disassemble the detector to clean.  

 

 

If the detector is not operating properly after cleaning, replace detector.

b. PAD100-PD: When cleaning is needed, follow the below steps to remove dust 

  on the detector

Alarm Set-Point

Rate of Rise Spacing

Fixed Temperature Spacing

135

O

 to 174

F

(57

O

 to 79

O

 C)

Maximum 60 ft.

Maximum 60 ft.

175

O

 to 185

F

(80

O

 to 85

O

 C)

Maximum 15 ft.

Maximum 15 ft.

135

O

 to 160

F

(57

O

 to 71

O

 C)

Maximum 70 ft.

Maximum 70 ft.

Alignment 

Features

Mount the 

PAD100-LFSB / 

PAD100-SPKB base to the 

electrical box using the 

provided mounting 

screws.

FIGURE 6a: 

Assembly of Detector on Electrical Box

Four screws are 

provided, two for 

securing speaker 

to the back box 

and two for 

aesthetics. The 

two non-functional 

screws will be held 

in place by the 

pressure fit of the 

faceplate.

FIGURE 6b: 

Assembly of Detector on LFSBBB-W Back Box

Alignment 

Features

Mount the 

PAD100-LFSB / 

PAD100-SPKB base to the 

LFSBBB-W Back Box using 

the provided mounting 

screws.

Summary of Contents for PAD100-LFSB

Page 1: ...K WIRE RUN TO PROVIDE SUPERVISION OF CONNECTION CAUTION Break wire runs to provide supervision for connections made to each wire pair When installing route field wiring away from sharp projections corners and internal components Detector Base Mounting PAD100 LFSB PAD100 SPKB should be mounted directly on the electrical box FIGURE 6a or to the LFSBBB W back box FIGURE 6b The PAD100 LFSB PAD100 SPKB...

Page 2: ...e Safeguard Model 25S or SDi Smoke Centurion as acceptable to the Authority Having Jurisdiction AHJ b PAD100 PHD and PAD100 HD Heat Detectors NOTICE TAKE CARE DURING THE HEATING OF THE DETECTOR TO AVOID OVERHEATING THE PLASTIC HOUSING Use of a low powered heat gun is acceptable CAUTION Do not heat over 210o F 98 9o C Maintain a minimum of 1 foot between the detector and the heat gun nozzle Heat th...

Page 3: ...hat locks the detector and does not allow removal without the use of a tool 1 Once the detector has been installed the detector locks into the base To remove the detector from the base insert a small screwdriver into the slot on the detector FIGURE 11 and push the plastic tab while simultaneously turning the detector head counter clockwise 2 The locking feature can be disabled To disable the locki...

Page 4: ...tandby Current 300 µA 3 Alarm Indicator 1 LED 4 Alarm Indictor Current 1 4 mA 5 Alarm Set Point Range 1 0 3 7 ft 3 6 12 m 1 0 3 7 ft 3 6 12 m 135O to 174O F 57O to 79O C 135O to 174O F 57O to 79O C 175O to 185O F 80O to 85O C 135O to 160O F 57O to 71O C Fixed 70 150 400 PPM 6 Installation Temperature Range 32O to 120O F 0O to 49O C 32O to 115O F 0O to 46O C 32O to 100O F 0O to 38O C 32O to 150O F ...

Page 5: ...ce either amplifier input or gain PAD100 SPKB Field Selectable Power Tap Selection Reverberant dBA 10ft Voltage 1 8 Watt 1 4 Watt 1 2 Watt 1 Watt 2 Watt 4 Watt 25 Volts 75 0 dBA 78 1 dBA 81 2 dBA 83 8 dBA 86 6 dBA 89 7 dBA 70 7 Volts 75 1 dBA 78 1 dBA 80 9 dBA 83 8 dBA 86 9 dBA 89 6 dBA 11 PAD Protocol Dip Switch Settings The following information is for setting the dipswitches on the PAD100 PD PA...

Page 6: ...er Electric Signal Company LLC personnel at Potter Electric Signal Company LLC s facilities in Hazelwood Missouri You must also pack the appliance to minimize the risk of it being damaged in transit If we receive an appliance in a damaged condition as the result of shipping we will notify you and you must seek a claim with the shipper If you submit a valid claim to Potter Electric Signal Company L...

Reviews: