4. Use
Parameters table
N°
Description
Adjustment range
Factory setting
Remarks
01*
Adjustment of temperature difference before restart
1~18°C
1°C
Adjustable
02
Reserved - Do not adjust
--
--
Reserved
03
Reserved - Do not adjust
--
--
Reserved
04
Adjusting the cooling temperature
8~28°C
27°C
Adjustable
05
Adjusting the heating temperature
15~40°C
27°C
Adjustable
06
Setting temp for exhaust temp too high protection
80°C~125°C
120°C
Adjustable
07
Exhaust temp too high protection recover setting temp
50°C~100°C
95°C
Adjustable
08
Compressor current protection
2A~50A
--
Reserved
09
Setting the compensation coefficient of the temperature water inlet
-5~15°C
0°C
Adjustable
10
Reserved - Do not adjust
--
--
Reserved
11
Auto-activation time before de-icing commences
20~90 min
45 min
Adjustable
12
De-icing activation temperature
-15~1°C
-3°C
Adjustable
13
Maximum de-icing duration
5~20 min
8 min
Adjustable
14
De-icing deactivation temperature
1~40°C
20°C
Adjustable
15
Temp. difference between ambient and outside coil temp to enter
de-icing
0°C~15°C
0°C
Adjustable
16
Ambient temp to start de-icing
0°C~20°C
17°C
Adjustable
17
Expansive valve action period
20~90s
30s
Adjustable
18
Target over-heat temp during heating mode
-5°C~10°C
1°C
Adjustable
19
Exhaust temp adjusted by electrical expansive valve
70°C~125°C
95°C
Adjustable
20
The openness of electrical expansive valve during de-icing
20~450
300
Adjustable
21
The mini opening for the electrical expansive valve
50~150
100
Adjustable
22
Adjustment working mode of electrical expansive valve
0: manual / 1: auto
1
Adjustable
23
The manual step of electrical expansive valve
20~450
350
Adjustable
24
Target over-heat temp during cooling mode
-5°C~10°C
3°C
Adjustable
25
Reserved - Do not adjust
--
--
Reserved
26
Reserved - Do not adjust
--
--
Reserved
27
Working mode of electrical expansive valve during cooiling mode
0=ambient
temp(A03)/1=real over-
heat temp(parameter
A05-A07)
1
Adjustable
28**
Filtration pump servo-control mode
0 ~ 1
1
Adjustable
*
Parameter 01 allows you to change the lost degree interval from the requested temperature so that the heat pump starts again.
Example : If the value of parameter 01 is 3°C, after reaching the required temperature (eg 27°C), the heat pump will restart when the pool tempe
-
rature drops to 24°C (27 - 3).
*
*
Parameter 28: Control mode of the circulation pump
When you switch on your heat pump, the circulation pump starts and then 1 minute later, the heat pump compressor is activated. When
the heat pump stops running, its compressor and fan shut off, and after 30 seconds, the circulation pump stops. During a defrost cycle, the
circulation pump will continue to operate regardless of the mode chosen.
Mode 1 :
By selecting this mode, the heat pump will automatically put the circulating pump into continuous operation. Once the circulating pump is
operating, the heat pump will start up 1 minute later. Next, when the required temperature is reached, the heat pump will stop working but will not
stop the circulating pump, so as to ensure a constant circulation of water in your heat pump.
Mode 0 :
This mode has been designed to maintain filtration in your pool without using the timetable programmer. When the required
temperature is reached, the heat pump will go on standby, then 30 seconds later the circulating pump will shut down. It is only when the pool
temperature goes down by 1°C (Parameter 01) in relation to the required temperature that the filtration pump and the heat pump resume their
normal operating mode. (This mode is recommended for a direct connection allowing a delayed start of the circulation pump and the heat
pump without going through the timer the circulation pump).