background image

© 2017 PoolPak LLC. All rights reserved.

Page 4

MPK with CommandPak

 Control System BACnet /IP User’s Guide

The following table lists the available points along with their object types and instance numbers.

OBJECT 

TYPE

READ/ 

WRITE

OBJECT 

INSTANCE

OBJECT NAME

DESCRIPTION

UNITS

AV

R

1

CPR1_xwfCprCur

System 1 Cmpr Current

Amps

AV

R

2

CPR2_xwfCprCur

System 2 Cmpr Current

Amps

AV

R

3

CPR3_xwfCprCur

System 3 Cmpr Current

Amps

AV

R

4

xwfAirOffEvpRelHum

Air Leaving Evap Rel Humidity (RH)

%

AV

R

5

xwfAirOffEvpTmp

Air Leaving Evap Temperature

°C

AV

R

6

xwfAuxAirCoolPercent

Aux Air Cooling Percent Output

%

AV

R

7

xwfAuxAirHeatPercent

Actual Aux Air Heating % Output

%

AV

R

8

xwfAuxAirHeatPercent_1

Calc Aux Air Heating % Output

%

AV

R

9

xwfExhAirVol

Exhaust Air Volume

CFM

AV

R

10

xwfExhFanCur

Exhaust Fan Current

Amps

AV

R

11

xwfMixBoxPctOpen

Mixing Box Position

%

A

V

R

12

xwfOutAirDewpoint

Outside Air Dewpoint

°C

AV

R

13

xwfOutAirRelHum

Outside Air RH

%

AV

R

14

xwfOutAirTmp

Outside Air Temperature

°C

AV

R

15

xwfOutAirVol

Outside Air Volume

CFM

AV

R

16

xwfOutDprFbk

Outside Air Damper Position

%

AV

R

17

xwfPool1WtrTmp

Pool1 Water Temperature

°C

AV

R

18

xwfPool2WtrTmp

Pool2 Water Temperature

°C

AV

R

19

xwfPurAirVol

Purge Air Volume

CFM

AV

R

20

xwfPurFanC

ur

Purge Fan Current

Amps

AV

R

21

xwfRtnAirDewpoint

Return Air Dewpoint

°C

AV

R

22

xwfRtnAirRelHum

Return Air RH

%

AV

R

23

xwfRtnAirTmp

Return Air Temperature

°C

AV

R

24

xwfSetEvtMinMixBoxPos

Event Min Mix Box Position

%

AV

R

25

xwfSetMaxMixBoxPos

Max Mix Box Position

%

AV

R

26

xwfSetMinMixBoxPos

Min Mix Box Position

%

AV

R

27

xwfSetPool1WtrTmp

Pool1 Water Temp Setpoint

°F

AV

R

28

xwfSetPool2WtrTmp

Pool2 Water Temp Setpoint

°F

AV

R

29

xwfSetRtnAirRelHum

Return Air RH Setpoint

%

AV

R

30

xwfSetRtnAirTmp

Return Air Temp Setpoint

°F

AV

R

31

xwfSupAirTmp

Supply Air Temperature

°C

AV

R

32

xwfSupAirVol

Supply Air Volume

CFM

AV

R

33

xwfSupFanCur

Supply Fan Current

Amps

AV

R

34

xwfSurTmp

Surface Temperature

°C

AV

R

1001

CPR1_xwiActiveFaultCode

Cmpr1 Fault Code

See

 

below

AV

R

1002

CPR1_xwiMode

Cmpr1 Actual Mode

See below

Summary of Contents for MPK series

Page 1: ...DOCUMENT SVW07 MPKBACNIP 20171020 UPDATED OCTOBER 2017 PoolPak MPK with CommandPak Control System CPCS BACnet IP User s Guide...

Page 2: ...advanced password of 9995 then press Enter 6 Use the arrow keys to scroll down to BAS Interface then press Enter 7 Press the Enter key to move the cursor to different fields Use the arrow keys to chan...

Page 3: ...the following address in a web browser http IP Address config where IP Address is the address assigned to the card manually or through a DHCP server The computer used must be on the same subnet as th...

Page 4: ...side Air RH AV R 14 xwfOutAirTmp Outside Air Temperature C AV R 15 xwfOutAirVol Outside Air Volume CFM AV R 16 xwfOutDprFbk Outside Air Damper Position AV R 17 xwfPool1WtrTmp Pool1 Water Temperature C...

Page 5: ...1ModeReq Cmpr1 Mode Requested Stages AV R 1018 xwiCpr2ModeReq Cmpr2 Mode Requested Stages AV R 1019 xwiCpr3ModeReq Cmpr3 Mode Requested Stages AV R 1020 xwiDehStgRqd Dehumidification Stages Rqd Stages...

Page 6: ...Modes Requested are enumerated values indicating the operation mode of the corresponding compressor system The present value for these objects can be decoded as follows 0 Compressor Off 1 Air Heating...

Page 7: ...ressure drop UNIT FAULT CODE AND LAST UNIT FAULT CODE XWIUNITGNLFLTCODE AV1022 and AV1024 are enumerated values indicating a general fault condition for the unit The last fault AV1022 indicates the mo...

Page 8: ...resented by integer values in degrees Fahrenheit CONTROLLING OCCUPANCY MODE The BAS can control the dehumidifier s Purge mode directly This control overrides all internal schedules and controls except...

Page 9: ...uested set point change is outside of the acceptable range Select set points based on the acceptable range 3491 Industrial Drive York Pennsylvania 17402 USA 800 959 7725 Fax 717 757 5085 2017 PoolPak...

Reviews: