INTRODUCTION

PoolPak

®

 dehumidifiers equipped with an CommandPak

 Control 

System (CPCS) can be directly connected to a BACnet/IP based 
Building Automation System (BAS). Based on Carel’s pcoWeb serial 
card, the interface allows connection to an Ethernet network. 80 control 
points, including all basic information and set points for the PoolPak 
dehumidification system, are available through the interface.

COMMANDPAK

 CONTROL SYSTEM CONFIGURATION FOR BACNET

PoolPak

®

 dehumidifiers equipped with CPCS can be directly connected to a BACnet/IP based Building Automation System 

(BAS). Based on Carel’s pcoWeb serial card, the interface allows connection to an Ethernet network. 80 control points, 
including all basic information and set points for the PoolPak dehumidification system, are available through the interface.

The BACnet configuration parameters for the controller are accessed in the configuration menu. To access this menu:

1. Press the program key (

) on the RIU or CM1 module

2. Scroll down to “Service” then press Enter (

).

3. Scroll up for the service password “0005”, then press Enter (

).

4. Scroll down to “Unit Config” then press Enter (

).

5. Scroll down for the advanced password of “9995”, then press Enter (

).

6. Use the arrow keys to scroll down to “BAS Interface”, then press Enter (

).

7. Press the Enter key 

 to move the cursor to different fields. Use the arrow keys to change the following parameters  

as needed:

•  TYPE

 – 

BACnet

 – This is the type of BAS system connecting.

•  BAUD RATE

 – 

19200

 – Sets the baud rate for the onboard serial port. It must be set to 19200 for use with the 

BACnet interface. 19200 is the factory default setting for this parameter. Note that this is the baud rate of the 
internal serial interface between the BACnet board and the PoolComPak controller. The baud rate of the BACnet 
MS/TP connection is set with a utility program from Carel. See the Interface Card Field Setup and Configuration 
section of this document for more information.

•  BAS Addr

 – 

001

 – Sets the address of the BACnet interface card in the serial slot of the controller. It must be 

set to 1 for proper operation of the BACnet interface. The factory default setting is 1. Note that this is the internal 
serial address of the BACnet board. The station address for the BACnet MS/TP network is set with a utility program 
from Carel. See the Interface Card Field Setup and Configuration section of this document for more information.

8.  After changing any of the above parameters, reboot the controller by cycling power with the unit control power 

switch. This switch is located within or adjacent to the main control panel of the dehumidifier.

Summary of Contents for MPK series

Page 1: ...DOCUMENT SVW07 MPKBACNIP 20171020 UPDATED OCTOBER 2017 PoolPak MPK with CommandPak Control System CPCS BACnet IP User s Guide...

Page 2: ...advanced password of 9995 then press Enter 6 Use the arrow keys to scroll down to BAS Interface then press Enter 7 Press the Enter key to move the cursor to different fields Use the arrow keys to chan...

Page 3: ...the following address in a web browser http IP Address config where IP Address is the address assigned to the card manually or through a DHCP server The computer used must be on the same subnet as th...

Page 4: ...side Air RH AV R 14 xwfOutAirTmp Outside Air Temperature C AV R 15 xwfOutAirVol Outside Air Volume CFM AV R 16 xwfOutDprFbk Outside Air Damper Position AV R 17 xwfPool1WtrTmp Pool1 Water Temperature C...

Page 5: ...1ModeReq Cmpr1 Mode Requested Stages AV R 1018 xwiCpr2ModeReq Cmpr2 Mode Requested Stages AV R 1019 xwiCpr3ModeReq Cmpr3 Mode Requested Stages AV R 1020 xwiDehStgRqd Dehumidification Stages Rqd Stages...

Page 6: ...Modes Requested are enumerated values indicating the operation mode of the corresponding compressor system The present value for these objects can be decoded as follows 0 Compressor Off 1 Air Heating...

Page 7: ...ressure drop UNIT FAULT CODE AND LAST UNIT FAULT CODE XWIUNITGNLFLTCODE AV1022 and AV1024 are enumerated values indicating a general fault condition for the unit The last fault AV1022 indicates the mo...

Page 8: ...resented by integer values in degrees Fahrenheit CONTROLLING OCCUPANCY MODE The BAS can control the dehumidifier s Purge mode directly This control overrides all internal schedules and controls except...

Page 9: ...uested set point change is outside of the acceptable range Select set points based on the acceptable range 3491 Industrial Drive York Pennsylvania 17402 USA 800 959 7725 Fax 717 757 5085 2017 PoolPak...

Reviews: