MPK with CommandPak

 Control System BACnet /IP User’s Guide

INTERFACE CARD FIELD SETUP AND CONFIGURATION

The BACnet interface card is shipped from the factory with the following default settings:

•  DHCP: ON
•  IP Address: — . — . — . —
•  Netmask: — . — . — . —
•  Gateway: — . — . — . —
•  DNS1: — . — . — . —
•  DNS2: — . — . — . —

•  BACnet ID (Device Instance): 77000

•  BACnet Type: IP

Change the above card settings on the controller or keypad as follows:

1.  Press and hold the Alarm ( ) and Enter (

) keys.

2.  Arrow down to “Other Information” then press Enter (

)

3.  Arrow down to “PCOWEB/NET CONFIG” then press Enter (

)

4.  Arrow down to “PCOWEB,” then press Enter (

). (PCONET is for MS/TP)

5.  Use the Enter (

) key to move the cursor to the value you need to change. Use the arrow keys to change the value.

6.  The last screen will say “pCONET CONFIG ENABLE”, then “Update pCOnet?” Select “YES” then press Enter (

).

7.  After changing any of the above parameters, reboot the controller by cycling power with the unit control  

power switch.

The above parameters along with UDP Port, Description, and Location can be changed through the web interface available 
through the Ethernet connection on the BACnet card. To access this page, enter the following address in a web browser: 
http://”IP Address”/config where IP Address is the address assigned to the card manually or through a DHCP server.  
The computer used must be on the same subnet as the BACnet card. Contact PoolPak Service at 800-959-7725 for login 
information.

For any difficulty changing these parameters, contact PoolPak Service at 800-959-7725 for assistance.

PHYSICAL NETWORK CONNECTION

The 8P8C (“RJ-45”) Ethernet socket is located on the pCOWeb interface card. The pCOWeb card occupies the serial card 
slot directly below the keypad built into the CM1 control module. This control module is located in the main control panel 
of the PoolPak dehumidifier.

The Ethernet connection to the interface card should comply with standard installation practices. Use care to route the cable 
away from sources of interference and keep the maximum cable length less than 300 feet.

CONTROL POINTS MAPPING

80 objects are accessible through the BACnet interface. Set points, sensor values, and enumerated variables are shared 
as analog-value objects. Status information points are shared as binary-value objects. The interface card is pre-configured 
at the factory with a device instance number of 77000. To change this value, follow the instructions shown in the Interface 
Card Field Setup and Configuration section of this document.

Summary of Contents for MPK series

Page 1: ...DOCUMENT SVW07 MPKBACNIP 20171020 UPDATED OCTOBER 2017 PoolPak MPK with CommandPak Control System CPCS BACnet IP User s Guide...

Page 2: ...advanced password of 9995 then press Enter 6 Use the arrow keys to scroll down to BAS Interface then press Enter 7 Press the Enter key to move the cursor to different fields Use the arrow keys to chan...

Page 3: ...the following address in a web browser http IP Address config where IP Address is the address assigned to the card manually or through a DHCP server The computer used must be on the same subnet as th...

Page 4: ...side Air RH AV R 14 xwfOutAirTmp Outside Air Temperature C AV R 15 xwfOutAirVol Outside Air Volume CFM AV R 16 xwfOutDprFbk Outside Air Damper Position AV R 17 xwfPool1WtrTmp Pool1 Water Temperature C...

Page 5: ...1ModeReq Cmpr1 Mode Requested Stages AV R 1018 xwiCpr2ModeReq Cmpr2 Mode Requested Stages AV R 1019 xwiCpr3ModeReq Cmpr3 Mode Requested Stages AV R 1020 xwiDehStgRqd Dehumidification Stages Rqd Stages...

Page 6: ...Modes Requested are enumerated values indicating the operation mode of the corresponding compressor system The present value for these objects can be decoded as follows 0 Compressor Off 1 Air Heating...

Page 7: ...ressure drop UNIT FAULT CODE AND LAST UNIT FAULT CODE XWIUNITGNLFLTCODE AV1022 and AV1024 are enumerated values indicating a general fault condition for the unit The last fault AV1022 indicates the mo...

Page 8: ...resented by integer values in degrees Fahrenheit CONTROLLING OCCUPANCY MODE The BAS can control the dehumidifier s Purge mode directly This control overrides all internal schedules and controls except...

Page 9: ...uested set point change is outside of the acceptable range Select set points based on the acceptable range 3491 Industrial Drive York Pennsylvania 17402 USA 800 959 7725 Fax 717 757 5085 2017 PoolPak...

Reviews: