MPK with CommandPak
™
Control System BACnet /IP User’s Guide
INTERFACE CARD FIELD SETUP AND CONFIGURATION
The BACnet interface card is shipped from the factory with the following default settings:
• DHCP: ON
• IP Address: — . — . — . —
• Netmask: — . — . — . —
• Gateway: — . — . — . —
• DNS1: — . — . — . —
• DNS2: — . — . — . —
• BACnet ID (Device Instance): 77000
• BACnet Type: IP
Change the above card settings on the controller or keypad as follows:
1. Press and hold the Alarm ( ) and Enter (
) keys.
2. Arrow down to “Other Information” then press Enter (
)
3. Arrow down to “PCOWEB/NET CONFIG” then press Enter (
)
4. Arrow down to “PCOWEB,” then press Enter (
). (PCONET is for MS/TP)
5. Use the Enter (
) key to move the cursor to the value you need to change. Use the arrow keys to change the value.
6. The last screen will say “pCONET CONFIG ENABLE”, then “Update pCOnet?” Select “YES” then press Enter (
).
7. After changing any of the above parameters, reboot the controller by cycling power with the unit control
power switch.
The above parameters along with UDP Port, Description, and Location can be changed through the web interface available
through the Ethernet connection on the BACnet card. To access this page, enter the following address in a web browser:
http://”IP Address”/config where IP Address is the address assigned to the card manually or through a DHCP server.
The computer used must be on the same subnet as the BACnet card. Contact PoolPak Service at 800-959-7725 for login
information.
For any difficulty changing these parameters, contact PoolPak Service at 800-959-7725 for assistance.
PHYSICAL NETWORK CONNECTION
The 8P8C (“RJ-45”) Ethernet socket is located on the pCOWeb interface card. The pCOWeb card occupies the serial card
slot directly below the keypad built into the CM1 control module. This control module is located in the main control panel
of the PoolPak dehumidifier.
The Ethernet connection to the interface card should comply with standard installation practices. Use care to route the cable
away from sources of interference and keep the maximum cable length less than 300 feet.
CONTROL POINTS MAPPING
80 objects are accessible through the BACnet interface. Set points, sensor values, and enumerated variables are shared
as analog-value objects. Status information points are shared as binary-value objects. The interface card is pre-configured
at the factory with a device instance number of 77000. To change this value, follow the instructions shown in the Interface
Card Field Setup and Configuration section of this document.