MPK with CommandPak

 Control System BACnet /IP User’s Guide

SYMPTOM

POSSIBLE CAUSE

SOLUTION

The dehumidifier cannot be seen  

on the BACnet network.

The interface card is not properly  

connected to the network.

Correct network wiring.

Power to the controller is off.

If safe to do so, turn on the main  

disconnect and the control power 

switch(CPS) in the control  

compartment of the dehumidifier.

The BAS is trying to access the interface  

with the wrong device instance number.

Follow the instructions in this  

document to set the instance number  

to a value appropriate for the BAS.

The variable values sent by the  

controller are different than  

those shown on the RIU.

Incorrect setting of the  

BAS configuration parameters  

in the service menu.

Correct the parameter values to match  

the settings shown in this document.

Set point changes are different  

than requested by the BAS.

Requested set point change is  

outside of the acceptable range.

Select set points based  

on the acceptable range.

3491 Industrial Drive

York, Pennsylvania 17402 USA

800-959-7725  Fax 717-757-5085

© 2017 PoolPak LLC. All rights reserved.   SVW07-MPKBACNIP-20171020

With more than 45 years of experience in indoor pool dehumidification equipment manufacturing, PoolPak

®

 LLC is the most well-known brand 

in the industry. Our people and products work daily to improve the quality and comfort of indoor pool environments. PoolPak

®

 dehumidification 

solutions include a variety of heating, ventilation, and air conditioning systems, in addition to an industry-leading PoolPak

®

 support network. For more 

information, please visit www.PoolPak.com.

For questions about the interface that are not answered in this document, 
please contact the PoolPak Service department at 800-959-7725.

BACnet

®

 is a registered trademark 

of American Society of Heating, 

Refrigerating and Air-Conditioning 

Engineers (ASHRAE). This 

trademark is used in the text, but 

for the sake of readability, it is not 

individually marked.

Summary of Contents for MPK series

Page 1: ...DOCUMENT SVW07 MPKBACNIP 20171020 UPDATED OCTOBER 2017 PoolPak MPK with CommandPak Control System CPCS BACnet IP User s Guide...

Page 2: ...advanced password of 9995 then press Enter 6 Use the arrow keys to scroll down to BAS Interface then press Enter 7 Press the Enter key to move the cursor to different fields Use the arrow keys to chan...

Page 3: ...the following address in a web browser http IP Address config where IP Address is the address assigned to the card manually or through a DHCP server The computer used must be on the same subnet as th...

Page 4: ...side Air RH AV R 14 xwfOutAirTmp Outside Air Temperature C AV R 15 xwfOutAirVol Outside Air Volume CFM AV R 16 xwfOutDprFbk Outside Air Damper Position AV R 17 xwfPool1WtrTmp Pool1 Water Temperature C...

Page 5: ...1ModeReq Cmpr1 Mode Requested Stages AV R 1018 xwiCpr2ModeReq Cmpr2 Mode Requested Stages AV R 1019 xwiCpr3ModeReq Cmpr3 Mode Requested Stages AV R 1020 xwiDehStgRqd Dehumidification Stages Rqd Stages...

Page 6: ...Modes Requested are enumerated values indicating the operation mode of the corresponding compressor system The present value for these objects can be decoded as follows 0 Compressor Off 1 Air Heating...

Page 7: ...ressure drop UNIT FAULT CODE AND LAST UNIT FAULT CODE XWIUNITGNLFLTCODE AV1022 and AV1024 are enumerated values indicating a general fault condition for the unit The last fault AV1022 indicates the mo...

Page 8: ...resented by integer values in degrees Fahrenheit CONTROLLING OCCUPANCY MODE The BAS can control the dehumidifier s Purge mode directly This control overrides all internal schedules and controls except...

Page 9: ...uested set point change is outside of the acceptable range Select set points based on the acceptable range 3491 Industrial Drive York Pennsylvania 17402 USA 800 959 7725 Fax 717 757 5085 2017 PoolPak...

Reviews: