background image

33

EGW06-PCPEG-20140813

TM

TM

Section IV: Installation

AUXILIARY POOL WATER HEATING SYSTEM (AWH MODEL ONLY*) (6)

The auxiliary pool water heating system is provided by others.  Typically a gas fired or electric pool water heater is used. 

The ECC-PCP provides a dry contact closure that signals a need for auxiliary water heating. The contacts of the ECC-

PCP may be connected directly to the heater’s control circuit provided the circuit is 24 VAC maximum and the current 

does not exceed 1 amp inductive. Any other applications will require an additional relay (by others) to be installed 

between the ECC-PCP and the pool water heating system.

AUXILIARY AIR HEATING SYSTEM (7)

Typically a duct mounted electric heater, hot water coil or a factory installed unit mounted hot water coil is used to 

provide air heating. The ECC-PCP provides a form “C” (NO and NC) dry contact closure that signals a need for 

auxiliary air heating. The ECC-PCP contacts may be directly connected to an electric duct heater control circuit provided 

the circuit is 24 VAC maximum and the current through the contacts does not exceed 1 amp inductive. The figure below 

shows a typical installation that utilizes a 3-way hot water control valve and a unit or duct mounted hot water coil.

Figure 4-7. Installation of a Hot Water Coil 3-Way Valve

PCP_EG_Optional3WayHotWaterValveInstall_20121204.eps

EXTERNAL ALARM SYSTEM (8)

The ECC-PCP provides a normally open contact closure for connection to a building management system. If a fault 

occurs, the controller will energize this output to indicate that there is a problem with the dehumidification system.  The 

remote interface unit will display the cause of the fault and provide a suggested course of action. This output may also be 

used to energize an external alarm light or buzzer. It may also be directly connected to an external circuit as long as the 

circuit is 24 VAC maximum and the current through the contacts does not exceed 1 amp inductive.

HO

WA

TER C

OIL

FIELD SUPPLIED

ACTUATOR

A/B SWITCH IN

B POSITION

2

1

W

BK

W 3

A

B

 VALVE IN BYPASS POSITION

HOT WATER IN

HOT WATER OUT

THREE WAY VALVE WITH
ACTUATOR

HO

WA

TER C

OIL

 VALVE IN HEATING POSITION

HOT WATER IN

HOT WATER OUT

THREE WAY VALVE WITH
ACTUATOR

ALL WIRING BY CONTRACTOR

T2.3

T2.5

T2.4

POOLCOMPAK

120 VAC

24 VAC

FIELD SUPPLIED 40 VA

TRANSFORMER

WIRING DETAIL

PIPING DETAIL

Summary of Contents for AW 0550

Page 1: ...AWH HCDH only POOLCOMPAK R 410A AW HCD SERIES ROOFPAK SERIES HCD High Capacity Dehumidifier AW Air and Water Horizontal H and Vertical V Configurations Engineering Guide EGW06 PCPEG 20140813 Packaged...

Page 2: ...TM TM 3491 Industrial Drive York PA 17402 USA 800 959 7725 Fax 717 757 5085 for more information www poolpak com The Leader in Indoor Pool Dehumidification TM TM...

Page 3: ...erature and Humidity 8 Room Dew Point Control 9 PoolComPak Operation 9 ECC PCP Control System 10 Overview 10 Humidity Control 10 Cold Surface Temperature Humidity Reset 10 Space Heating 10 Networking...

Page 4: ...iping 27 Curb Mounting 28 Integral Gas Furnace Option RoofPak Only 29 ECC PCP Controls Field Wiring 30 Overview 30 Remote Interface Unit 1 30 Cold Surface Temperature Sensor 2 31 Economizer System Opt...

Page 5: ...ts 47 ECC PCP Service 47 Service Menu 47 I O Configuration 47 Digital Inputs 47 Digital Outputs 47 Analog Inputs 48 Unit Configuration 48 Installed Options 48 Aux Air Heating 48 Aux Water Heating 48 T...

Page 6: ...mote ACC Installation When Installing Multiple Units 38 Figure 4 12 Remote ACC Installation When Installing Units in Pits 39 Figure 4 13 Remote ACC Installation When Installing Units Near Decorative F...

Page 7: ...nergy was used to bring in and heat the make up air and to heat the pool water More cost effective technologies offer an alternative method adding heat exchangers and mechanical heat recovery systems...

Page 8: ...common for seniors or children or less active pools The desirable humidity range is generally between 50 and 60 greater than 60 creates a sticky feeling and or difficult breathing and low humidity re...

Page 9: ...d but with modest operating cost Performance limitations in humid areas or during summer peaks No opportunity to recover energy into the pool water No integral cooling capability MECHANICAL DEHUMIDIFI...

Page 10: ...ified air back into it The supply air should be distributed over areas subject to condensation windows outside walls support trusses skylights etc AIRSIDE DESIGN The supply air volume and external sta...

Page 11: ...reasonable to avoid excessive noise in the ducts In multiple unit installations supply air from each unit may go into a common supply duct or into a plenum A supply air duct collar is provided at the...

Page 12: ...tandards and or generally accepted industry practice Supply and return duct work should have all seams sealed before applying insulation to the exterior of the duct work The insulation s seams must be...

Page 13: ...onnect the pool enclosure to the return air plenum collar of the PoolPak unit s Other Airside Considerations A hot water electric or gas duct heater may be installed in the supply duct to provide auxi...

Page 14: ...bove the pool water temperature Evaporation losses and the energy required to maintain desired room conditions will dramatically increase if the air temperature is allowed to fall below the pool water...

Page 15: ...es more than 1 2 degree Fahrenheit above the space dew point temperature set point the ECC PCP controller energizes the compressor for dehumidification As the dew point temperature drops more than 1 2...

Page 16: ...evaluation HUMIDITY CONTROL As the dewpoint temperature within the pool enclosure rises above the desired setpoint the ECC PCP activates the compressor within the PoolComPak to begin the dehumidifica...

Page 17: ...outside air temperature When appropriate the controller will disable the compressor and bring in cool outside air for economical operation A separate exhaust system must be installed to ensure negativ...

Page 18: ...denser for water heating or in the HCD Series without the pool water condenser Available Configurations Indoor Installation The PoolComPak fits easily into a standard utility room vertical and horizon...

Page 19: ...ngle power connection to minimize field wiring Separate power connection required for integral electric heat Durable Construction Heavy duty construction designed for outside installation to withstand...

Page 20: ...r mount design for easy service access to fan motor and belts Housed Blower Heavy pillow block bearings provide durability Rugged cast steel housing provides longevity Provides greater reliability Cup...

Page 21: ...ofPak Generic Product Drawings found in the Engineering Library section of the PoolPak website Model Number AWH HCDH 3500 10 Ton AWH HCDH 4000 12 Ton Pool Size Sq Ft 1 200 2 000 1 400 2 500 Reheat Cap...

Page 22: ...Air CFM Return Air RH Moisture removal lbs hr Sensible Cooling Capacity MBH ACC Max Heat Rejection MBH GPM Pressure Drop FT water 0550 900 60 11 1 13 6 31 2 4 6 50 8 5 15 6 30 1 0800 1600 60 15 7 22 1...

Page 23: ...600 60 14 5 20 8 46 2 50 10 3 23 9 44 4 1200 1700 60 19 0 25 2 56 4 50 14 5 28 4 54 4 1400 2300 60 24 1 36 2 74 7 50 17 9 40 5 71 8 1800 2500 60 28 9 41 8 88 1 50 20 9 47 4 84 6 2600 3300 60 41 0 53 5...

Page 24: ...1 Top OA Ho 41 1 41 1 41 1 43 0 43 0 61 1 61 1 61 1 Top OA Rainhood Hro 50 9 50 9 50 9 52 8 52 8 70 8 70 8 70 8 Length Basic L 60 1 60 1 60 1 72 0 72 0 92 1 92 1 92 1 Rear Return Lr 61 8 61 8 61 8 74...

Page 25: ...2 Side OA Wo 39 0 39 0 39 0 45 7 45 7 56 5 75 0 75 0 Height Basic H 49 3 49 3 49 3 55 9 55 9 60 5 60 5 60 5 Top OA Ho 56 3 56 3 56 3 62 9 62 9 67 5 67 5 67 5 Length Basic L 26 2 26 2 26 2 27 8 27 8 4...

Page 26: ...GPM Heating Capacity Range MBH Min Max Min Max 0550 5 15 33 54 0800 5 15 43 66 1200 5 15 48 75 1400 10 25 71 105 1800 10 25 80 111 2600 15 35 104 161 3500 20 40 147 203 4000 20 40 158 209 Horizontal...

Page 27: ...OA LT V3500 4000 Top A 14 x 10 OA TR 0 800 Left OA LT Top C 14 x 30 OA TR 800 2800 Left OA LT PoolComPak Horizontal AWH HCDH H550 800 1200 Top A 12 x 12 OA TC 0 450 Front OA FC Top B 12 x 24 OA TC 45...

Page 28: ...4 2 and Table 4 3 in the Installation section Unit Factory Charge1 R410A Air Cooled Condenser ACC Water Cooled Condenser WCC Model lbs oz lbs oz 0550 14 3 9 9 0800 15 5 10 7 1200 18 2 13 4 1400 24 13...

Page 29: ...3 8 1 9 ACC0051 110 3 4 1 2 120 ACC0081 115 7 8 5 8 210 1200 ACC0051 95 100 105 39 3 3 4 1 2 120 3 1 5 3 8 1 9 ACC0081 110 7 8 5 8 210 ACC0121 115 39 3 1 1 8 3 4 470 6 3 7 5 3 8 1400 1800 ACC0081 95...

Page 30: ...ndenser Bohn Elevation Views PCP_EG_ACC_Bohn_20140122 eps SINGLE FAN DUAL FAN ALL DIMENSIONS ARE IN INCHES 45 4 42 3 43 130 120 38 49 1 24 5 16 21 5 9 8 OPTIONAL EXTERNAL ELECTRICAL BOX 1 17 34 0 875...

Page 31: ...on three sides to match heater flanges as shown 2 Fasten heater to duct using sheet metal screws for smaller heaters or bolts for larger ones 3 Seal opening with suitable sealing compound 4 If needed...

Page 32: ...m Outside air can be ducted into the unit through the optional outside air duct connection The unit can draw up to 30 of its supply air from the outside When ventilating the natatorium in this way an...

Page 33: ...ring transit POWER SUPPLY A separate fused disconnect switch must be provided per local codes and be within easy accessibility of the PoolComPak unit Use the minimum circuit capacity listed on the uni...

Page 34: ...b to the bottom of the PoolComPak using the gasket supplied with the curb Provide counter flashing between curb and PoolComPak unit Seal the pool water pipes where they go through the curb If specifie...

Page 35: ...iping for the gas fired heater Pressures should be regulated to the entering pressures as shown on the furnace manufacturer s data plate or manual Model 550 800 1200 1400 1800 2600 3500 4000 2600 3500...

Page 36: ...ct the factory The control panel does not contain any sensors and should be mounted outside the pool enclosure A factory supplied 6 ft cable RJ25 6 conductor must be installed between the PoolComPak u...

Page 37: ...the ECC PCP may be connected directly to the economizer control circuit provided the circuit is 24 VAC maximum and the current does not exceed 1 amp inductive The other components of the system must...

Page 38: ...ng the economizer mode of operation If possible mount the sensor under an overhang or on a surface with a northern exposure Electrical connection should be made with 22 AWG copper 2 conductor shielded...

Page 39: ...acts does not exceed 1 amp inductive The figure below shows a typical installation that utilizes a 3 way hot water control valve and a unit or duct mounted hot water coil Figure 4 7 Installation of a...

Page 40: ...stream of the exhaust duct connection See Figure 4 4 Economizer Operation for a typical location of the sensor in the economizer system When field mounting is necessary the sensor will be provided fro...

Page 41: ...be used CAUTION CAUTION Excessive water flow can cause premature erosion and pitting of the pool water condenser Adjust valve so that the water flow does not exceed the GPM or pressure drop listed in...

Page 42: ...recommended that building materials subjected to the condensate and systems used for its disposal are checked for compatibility For drain piping use PVC plastic pipe minimum Schedule 40 The drain line...

Page 43: ...ideration which must be taken is that the unit should be mounted away from noise sensitive spaces and must have adequate support to avoid vibration and noise transmission into the building Units shoul...

Page 44: ...e Units ALL_MultipleUnits_20131111 eps Units in Pits The top of the unit should be level with the top of the pit and side distances increased to 2W If the top of the units is not level with the top of...

Page 45: ...erant pressure drops Use long radius elbows wherever possible with one exception short radius elbows should be used for any traps in the hot gas riser Braze all copper to copper joints with a phosphor...

Page 46: ...aining back to the compressor during OFF cycles Use the following guidelines The highest point in the discharge line should be above the highest point in the condenser coil The hot gas line should loo...

Page 47: ...ompressor installed For Copeland compressors use Copeland Ultra P N 998 E022 00 For Trane compressors use Trane P N OIL00080 Sample Charging Calculation For an AWV2600 with 73 feet line length and ACC...

Page 48: ...92 1 11 3 6 5 1 6 13 0800 5 8 0 16 3 8 0 49 1 0 2 1 3 1 4 2 5 8 0 16 1 2 0 92 1 11 3 6 5 1 6 13 1200 5 8 0 16 1 2 0 92 1 11 3 6 5 1 6 13 3 4 0 25 5 8 1 48 2 11 5 6 8 1 10 13 1400 5 8 0 16 1 2 0 92 1 1...

Page 49: ...also rotate automatically every 10 seconds Figure 5 2 Status Screen 1 S P A C E T E M P _ _ o F S P A C E R H _ _ S P A C E D E W P O I N T _ _ o F O U T S I D E T E M P _ _ o F Status Screen 1 displ...

Page 50: ...0 to 65 F Use the arrow keys to change the set point and then press Enter The new dew point set point is shown immediately as DPT The set point change screen will remain visible for a short time to al...

Page 51: ...re in the discharge line at the compressor Suct Press The measured refrigerant pressure in the suction line at the compressor Suct Temp The refrigerant temperature measured on the surface of the sucti...

Page 52: ...t will control water temperature based on the master s command NETWORK or its own temperature sensor and set point LOCAL If a unit set to LOCAL becomes the master other units in the network will not u...

Page 53: ...unit is displaying the unit they will be changed in all units configured for Network control The water temperature set point will only be changed in the unit currently being displayed by the remote in...

Page 54: ...vailable Discharge Pressure Suction Pressure Return Relative Humidity Suction Temperature Return Air Temperature Pool Water Temperature Surface Temperature Outside Air Temperature UNIT CONFIGURATION I...

Page 55: ...ehumidifier compressor ECONOMIZER This menu contains parameters that configure the operation of the optional field provided and field installed economizer damper system HISTORY The history screen prov...

Page 56: ...e scroll does not rub the housing Check for proper belt tension Worn or cracked belts should be replaced Check fan and mounting brackets for tightness Ensure that the ALARM light is not illuminated AN...

Page 57: ...0140813 TM TM SECTION VI WIRING AUXILIARY AIR POOL WATER HEATER CONNECTIONS FOR MULTIPLE UNIT INSTALLATION Figure 6 1 Auxiliary Air and Pool Water Heater Connections for Multiple Units AWH_EG_Connecti...

Page 58: ...13 TM TM AUXILIARY AIR POOL WATER HEATER CONNECTION FOR A TWO POOL INSTALLATION Figure 6 2 Auxiliary Air and Pool Water Heater Connections for Two Pool Installations AWH_EG_ConnectionstoPool_20121204...

Page 59: ...53 EGW06 PCPEG 20140813 TM TM Section VI Wiring FIELD WIRING Figure 6 3 Field Wiring Diagram PCP_EG_FieldWiringDiagram_20121204 eps...

Page 60: ...54 EGW06 PCPEG 20140813 TM TM Section VI Wiring FIRE CONTROL SYSTEM CONNECTION Figure 6 4 Fire Control System Connection PCP_EG_FirecontrolSysConnection_20121204 eps...

Page 61: ...55 EGW06 PCPEG 20140813 TM TM Section VI Wiring This page intentionally left blank...

Page 62: ...EGW06 PCPEG 20140813 TM TM 56 TM TM 3491 Industrial Drive York PA 17402 USA 800 959 7725 Fax 717 757 5085 for more information www poolpak com The Leader in Indoor Pool Dehumidification...

Reviews: