Menu
Code
Function
Setting
Range
Default
Setting
Remarks
TS1
Heating
Temperature Setpoint
-19.9~TS2
77 °F
1.1
HD
Heating Differential Value
0.5~30.0
3 °F
TS2
Cooling
Temperature Setpoint
TS1~199.9
88 °F
CD
Cooling Differential Value
0.5~30.0
3 °F
PT
Compressor Delay
0 ~ 15 min
0
1.2
Hr
High Alarm Limit
-19.9~199.9
180 °F
-
Lr
Low Alarm Limit
-19.9~199.9
-19.9 °F
CA
Temperature Calibration
-19.9 ~19.9°F 0°F
1.3
TS.2
TS1 Limit Adjust Reminder
Set TS2 larger
1.1
TS.1
TS2 Limit Adjust Reminder
Set TS1 smaller
1.1 Temperature Control Range Setting (TS1, HD, TS2, CD)
For example
, set TS1=77°F, HD=2°F, TS2=88°F and CD=3°F, then when
measured temperature is higher or equal to 91°F (TS2+CD) , system enters
refrigeration status; when temperature decline to 88°F(TS2), stop refrigeration;
when measured temperature is lower or equal to 75°F (TS1-HD), system enters
heating status; when the temperature raised to 77°F(TS1), stop heating.
Attentions:
TS1≤TS2, if you find TS1 can
’t be set any higher to 199.9 (or
TS2 can’t be set any lower to -19.9), please kindly set the TS2 value larger
(or set the TS1 smaller) first.