32
A12
Battery module high voltage
alarm
Stop charging the battery.
A13
Battery system low
environment temperature
alarm
Increase the environment
temperature.
A14
Battery system high
environment temperature
alarm
Lower the environment
temperature.
E01
Battery cell undervoltage
protection
Charge the battery.
E02
Battery cell overvoltage
protection
Wait 30 minutes. Reboot the
battery system if it’s not
recovered.
E03
Battery system
undervoltage protection
Charge the battery.
E04
Battery system overvoltage
protection
Wait 30 minutes. Reboot the
battery system if it’s not
recovered.
E05
Battery system charging low
temperature protection
Increase the battery temperature.
E06
Battery system charging
high temperature
protection
Lower the battery temperature.
E07
Battery system discharging
low temperature protection
Increase the battery temperature.
E08
Battery system discharging
high temperature
protection
Lower the battery temperature.
E09
Battery system charging
overcurrent protection
Lower the charging power and
reboot the battery system.
E10
Battery system discharging
overcurrent protection
Lower the discharging power and
reboot the battery system.