25
External Wiring
CAUTION: All cables shall be connected in sequence as listed in this
manual.
NOTE: The actual connection depends on your application case. Not all the
interfaces are used in every installation.
(1)
Refer to the table below for minimum copper wire sizing and ratings.
Voltage
Rating
Temp.
Class
Gauge
Ground
600V
75°C/167°F
6AWG (13.3mm2)
Battery
600V
75°C/167°F
10AWG (5.26mm2)
12Vdc
30V
60°C/140°F
24AWG (0.204mm2)
Ethernet
30V
60°C/140°F
Standard Ethernet cable
(2)
Connect Mega to ground (Torque: 3 N·m). Ensure installation is compliant
with local and national electrical codes.
(3)
Connect battery output to external PCS or other devices.
Summary of Contents for PBT-LI409100S2
Page 1: ...Mega Storage User Manual Published in January 2022 ...
Page 3: ...Legal Rights 37 Service 37 ...
Page 23: ...20 4 Plug all battery modules into the cabinet and fasten with M5 10 screws ...