PU1000/PU600 INSTALLATION MANUAL

 

  

 

 

                                            

 

10229-15.doc

Polyamp AB, Sweden 

www.polyamp.com 

Page 

10 (10) 

 

Some models have ”inrush current limit”. Fore 
further information consult 

9  Inrush current

 

limit on page

 8

2. 

 

The unit is broken. Contact your Polyamp 
dealer. 

 
11.3  The converter starts and stops 

repeatedly 

All models have an over/under voltage protection 
which shuts down the converter if the input voltage 
is not within specified limits (see front label).  

1.

 

The cables to the converter input may be under-
sized, causing too high voltage drop in the 
supply cables.  

2.

 

Your supply does not have enough current 
capacity so the input voltage to the converter 
drops below specified limit. 

 

11.4  The converter stops after several 

hours 

If the red ”OVER TEMP” LED is lit, the unit has 
not sufficient cooling or the ambient temperature is 
to high. See 

5.2  Over

 temperature on page 7 for 

further information. 

 

11.5  Fault report 

We suggest that you return a faulty converter to: 

POLYAMP AB 
Box 229 / Bäckgatan 10 
S-597 25  ÅTVIDABERG 
SWEDEN 
 
Tel: +46 120 85400 
Fax: +46 120 85405 
 
 

or to your local Polyamp distributor.  

To help us locate the fault, please describe the fault 
and how and when it occurred. 

Summary of Contents for PU1000

Page 1: ...PU1000 PU600 INSTALLATION MANUAL 10229 15 doc Polyamp AB Sweden www polyamp com Page 1 10 PU1000 PU600 Installation manual...

Page 2: ...information may have been updated since then Polyamp AB reserves the right to make changes in this manual without notice The exclamation point within an equilateral triangle is intended to alert the u...

Page 3: ...5 2 OVER TEMPERATURE 7 6 SENSE 7 6 1 EXTERNAL SENSE 7 6 2 INTERNAL SENSE 8 7 INHIBIT 8 8 OUTPUT OVER VOLTAGE PROTECTION 8 9 INRUSH CURRENT LIMIT 8 10 ISOLATION VOLTAGE TEST 8 10 1 DC ISOLATION TEST OU...

Page 4: ...l disconnection device which is able to disconnect both polarities shall be incorporated with the input power supply cord The disconnection device must be properly labelled and easy accessible 2 Insta...

Page 5: ...ly or if you require redundant operation If a converter breaks down with an internal short circuit on the output and other converters are connected in parallel on the output the broken unit will short...

Page 6: ...ntil the C MASTER LED is lit or almost lit 4 Multiple loads at the output If you are using several loads we recommend fusing them separately with fast acting fuses on the positive output branch Some c...

Page 7: ...r and connector pin marked NORMAL Figure 3 Alarm contact The relay is isolated 2500Va c from input output and case The relay can switch maximum 30V 5A a c and d c values 5 1 Over and under voltage ala...

Page 8: ...hibit 8 Output over voltage protection All models are equipped with an internal output over voltage protection circuit OVP It consists of an additional voltage regulator operating in parallel with the...

Page 9: ...solation test input to output and input to case above but test with 4000Vd c instead of 2000Vd c The leakage current should not exceed 5 A AC isolation test 1 Disconnect all cables from the converter...

Page 10: ...ay be under sized causing too high voltage drop in the supply cables 2 Your supply does not have enough current capacity so the input voltage to the converter drops below specified limit 11 4 The conv...

Reviews: