background image

The TUN-4046 heat detector covered by the present manual complies with the requirements of the 
following European Union Directives: 
 

CPR  

Regulation  (EU)  No.  305/2011  of  the  European  Parliament  and  of  the  Council  of  9  March 
2011  laying  down  harmonised  conditions  for  the  marketing  of  construction  products  and 
repealing Council Directive 89/106/EWG 

EMC

   2004/108/WE   on electromagnetic compatibility. 

 
The CNBOP-PIB, Notified Body No. 1438 has been issued for the product the national certificate of 
constancy  of  performance  confirming  the  possession  of  technical  features/parameters  required  by 
EN 54-5:2000+A1:2002, EN 54-17:2005+AC:2007. 
The  features/technical  parameters  above  that  exceeds  the  requirements  of  the  aforementioned 
standards are confirmed by the Manufacturer.  
Declaration of Performance has been issued for TUN-4046 
 
The certificate and the Declaration of Performance can be downloaded from 

www.polon-alfa.pl

 web 

site.

 

 
Read the manual carefully before the detector assembling and commissioning. 

Any  nonconformity  with  the  instructions  contained  in  the  manual  may  be  harmful  or  may  cause 
violation of the law in force  

POLON-ALFA  bears  no  responsibility  for  any  damage  resulting  from  usage  inconsistent  with  the 
manual. 

 

 

 

 

 

 

 

 

 

 
 

A  waste  product,  unsuitable  for  further  use,  shall  be  passed  to  
a waste electric and electronic equipment collection point. 

 

 

 

NOTE:  The manufacturer reserves the right to change specifications of products at any time 

without prior notice. 

 

Summary of Contents for TUN-4046

Page 1: ...STATE UNIVERSAL HEAT DETECTOR TUN 4046 POLON 4000INTERACTIVE FIRE DETECTION ANDALARM SYSTEM _________________________________________________________________________________ INSTALLATION AND MAINTENANCE MANUAL IK E283 001GB Edition IIIC ...

Page 2: ...007 The features technical parameters above that exceeds the requirements of the aforementioned standards are confirmed by the Manufacturer Declaration of Performance has been issued for TUN 4046 The certificate and the Declaration of Performance can be downloaded from www polon alfa pl web site Read the manual carefully before the detector assembling and commissioning Any nonconformity with the i...

Page 3: ...S Operating voltage 16 5 V 24 6 V Maximum quiescent mode current consumption 150 µA Detector class according to PN EN 54 5 standard A1 A2 B A2S BS A1R A2R BR Maximum installation height 7 5 m Maximum supervised area 30 m2 Other parameters acc to PN EN 54 5 standard Allowable relative humidity up to 95 at 40 C Minimum operating temperature 25 C Dimensions without base Ø 115 mm x 43 mm Mass without ...

Page 4: ...e consisting of a temperature sensitive resistor thermistor The thermistor protruding above the detector casing is located in the central point and protected against mechanical damages by a basket The detecting module is fastened to a printed board that contains all electronic elements and the detector operation monitoring processor The detector shape and construction enable free ambient air flow ...

Page 5: ...on the alarm mode is indicated with pulse red light emitted by the signalling diode The fault mode technical alarm and short circuit isolator actuation are signalled with yellow flashes of the illuminating diode The detector is furnished with a possibility to choose a way of reaction in the installation place pursuant to a given class It is the TUN 4046 heat detector so called operation mode A cho...

Page 6: ...e manual An additional optical alarm signal of a detector or a group of detectors can be obtained by connecting the WZ 31 alarm actuation indicator Alarm system cables are routed in accordance with low voltage system below 42V regulations as in force ATTENTION The detectors should not be installed in premises of corrosive atmosphere that contains caustic gases and vapours as well as high dust leve...

Page 7: ...IK E283 001GB 7 Fig 2 Clamps of base interoperating with TUN 4046 plug IK E283 001GB 06 2011 10 2021 ...

Page 8: ...8 IK E283 001GB ...