Polon-Alfa TUN-4046 Installation And Maintenance Manual Download Page 4

IK-E283-001GB 

 

3.2 Works at height  

Any detector installation works carried out at height must be executed with particular care utilising 
tools and machinery in good working condition.  

Special attention shall be given to stability of ladders, elevators, lifts, etc. 

Any  electric  tools  shall  be  used  strictly  obeying  the  safety  rules  stated  in  instruction  manuals  by 
manufacturers.  

3.3 Anti-dusting eye protection 

It  is  obligatory  to  use  protective  anti-dusting  glasses  and  masks  during  detector  installation  works 
that produce high amount of dust, such as hole drilling in ceilings. 

 

4  

DESIGN DESCRIPTIONS 

 

Fig. 1. TUN-4046 detector overall view 

 

The  detector  mechanical  construction  is  shown  in  Fig.  1.  Its  basic  element  is  a  detecting  module 
consisting  of  a  temperature-sensitive  resistor  (thermistor).  The  thermistor,  protruding  above  the 
detector  casing,  is  located  in  the  central  point  and  protected  against  mechanical  damages  by  a 
basket. The detecting module is fastened to a printed board that contains all electronic elements and 
the  detector  operation  monitoring  processor.  The  detector  shape  and  construction  enable  free 
ambient  air  flow  and  its  direct  impact  on  the  detecting  circuit.  The  whole  structure  is  placed  in  a 
white plastic housing containing a basket, detector cover, ring, and screen. 

The TUN-4046 detector is installed in the G-40 base where detection line cables are connected to. 

  

5  

PRINCIPLE OF OPERATION 

The  TUN-4046  heat  detector  reacts  to  a  rise  of  temperature  occurring  during  initial  phase  of  fire.  
The detector operates in two ways: 

-

 

as  a  fixed  temperature  detector 

  after  exceeding  its  set-up  temperature  activation 

threshold, pursuant to its given class; 

Summary of Contents for TUN-4046

Page 1: ...STATE UNIVERSAL HEAT DETECTOR TUN 4046 POLON 4000INTERACTIVE FIRE DETECTION ANDALARM SYSTEM _________________________________________________________________________________ INSTALLATION AND MAINTENANCE MANUAL IK E283 001GB Edition IIIC ...

Page 2: ...007 The features technical parameters above that exceeds the requirements of the aforementioned standards are confirmed by the Manufacturer Declaration of Performance has been issued for TUN 4046 The certificate and the Declaration of Performance can be downloaded from www polon alfa pl web site Read the manual carefully before the detector assembling and commissioning Any nonconformity with the i...

Page 3: ...S Operating voltage 16 5 V 24 6 V Maximum quiescent mode current consumption 150 µA Detector class according to PN EN 54 5 standard A1 A2 B A2S BS A1R A2R BR Maximum installation height 7 5 m Maximum supervised area 30 m2 Other parameters acc to PN EN 54 5 standard Allowable relative humidity up to 95 at 40 C Minimum operating temperature 25 C Dimensions without base Ø 115 mm x 43 mm Mass without ...

Page 4: ...e consisting of a temperature sensitive resistor thermistor The thermistor protruding above the detector casing is located in the central point and protected against mechanical damages by a basket The detecting module is fastened to a printed board that contains all electronic elements and the detector operation monitoring processor The detector shape and construction enable free ambient air flow ...

Page 5: ...on the alarm mode is indicated with pulse red light emitted by the signalling diode The fault mode technical alarm and short circuit isolator actuation are signalled with yellow flashes of the illuminating diode The detector is furnished with a possibility to choose a way of reaction in the installation place pursuant to a given class It is the TUN 4046 heat detector so called operation mode A cho...

Page 6: ...e manual An additional optical alarm signal of a detector or a group of detectors can be obtained by connecting the WZ 31 alarm actuation indicator Alarm system cables are routed in accordance with low voltage system below 42V regulations as in force ATTENTION The detectors should not be installed in premises of corrosive atmosphere that contains caustic gases and vapours as well as high dust leve...