PURPOSE 

The  TUN-4046  programmable  addressable  microprocessor  based  heat  detector  i

s  designed  for 

detection of a fire hazard or fire appearance indication in closed premises, where during the 
first  phase  of  fire  an  occurrence  of  temperature  rise  may  be  observed,  or  where  ambient 
temperature may exceed a set fire danger level. It

 enables programming of appropriate actions 

in the  place of installation that is it is possible  to set up the detector

’s

  class and its operation way 

according to the PN-EN 54-5 standard. The TUN-4046 detectors are dedicated for interoperation with 
the  POLON  4000  and  POLON  6000  fire  detection  and  alarm  systems.  They  operate  in  addressable 
loop-shaped  detection  lines  of  that  system.  Every  detector  is  equipped  with  a  program  controlled 
short circuit isolator.

 

 

2  

TECHNICAL SPECIFICATIONS 

Operating voltage 

16.5 V ÷ 24.6 V

 

Maximum quiescent mode current consumption 

≤ 150 µA

 

Detector class according to PN-EN 54-5 standard 

A1, A2, B, A2S, BS, A1R, A2R, BR 

Maximum installation height *) 

7.5 m  

Maximum supervised area *) 

30 m

2

  

Other parameters 

acc. to PN-EN 54-5 standard 

Allowable relative humidity 

up to 95 % at 40 °C

 

Minimum operating temperature 

-

25 °C 

 

Dimensions (without base) 

Ø 115 mm x 43 mm

 

Mass (without base) 

0.2 kg 

Standard colour 

white 

Detectors addresses range 

÷

 27  

Address coding method 

programmable at control panel 

 

*) TUN-4046 detectors should be installed (height, arrangement) in accordance with the Scientific and Research 

Centre for Fire Protection (CNBOP) design guidelines. 

 

3  

SAFETY CONDITIONS  

3.1 Repairs and maintenance  

Any maintenance works or periodic inspections shall be executed by skilled personnel employed by 
companies authorised and trained by POLON-ALFA.  

Any  repairs  must  be  carried  out  by  the  manufacturer.  POLON-ALFA  bears  no  responsibility  for  the 
operation of any apparatus being repaired by unauthorised personnel. 

Summary of Contents for TUN-4046

Page 1: ...STATE UNIVERSAL HEAT DETECTOR TUN 4046 POLON 4000INTERACTIVE FIRE DETECTION ANDALARM SYSTEM _________________________________________________________________________________ INSTALLATION AND MAINTENANCE MANUAL IK E283 001GB Edition IIIC ...

Page 2: ...007 The features technical parameters above that exceeds the requirements of the aforementioned standards are confirmed by the Manufacturer Declaration of Performance has been issued for TUN 4046 The certificate and the Declaration of Performance can be downloaded from www polon alfa pl web site Read the manual carefully before the detector assembling and commissioning Any nonconformity with the i...

Page 3: ...S Operating voltage 16 5 V 24 6 V Maximum quiescent mode current consumption 150 µA Detector class according to PN EN 54 5 standard A1 A2 B A2S BS A1R A2R BR Maximum installation height 7 5 m Maximum supervised area 30 m2 Other parameters acc to PN EN 54 5 standard Allowable relative humidity up to 95 at 40 C Minimum operating temperature 25 C Dimensions without base Ø 115 mm x 43 mm Mass without ...

Page 4: ...e consisting of a temperature sensitive resistor thermistor The thermistor protruding above the detector casing is located in the central point and protected against mechanical damages by a basket The detecting module is fastened to a printed board that contains all electronic elements and the detector operation monitoring processor The detector shape and construction enable free ambient air flow ...

Page 5: ...on the alarm mode is indicated with pulse red light emitted by the signalling diode The fault mode technical alarm and short circuit isolator actuation are signalled with yellow flashes of the illuminating diode The detector is furnished with a possibility to choose a way of reaction in the installation place pursuant to a given class It is the TUN 4046 heat detector so called operation mode A cho...

Page 6: ...e manual An additional optical alarm signal of a detector or a group of detectors can be obtained by connecting the WZ 31 alarm actuation indicator Alarm system cables are routed in accordance with low voltage system below 42V regulations as in force ATTENTION The detectors should not be installed in premises of corrosive atmosphere that contains caustic gases and vapours as well as high dust leve...

Page 7: ...IK E283 001GB 7 Fig 2 Clamps of base interoperating with TUN 4046 plug IK E283 001GB 06 2011 10 2021 ...

Page 8: ...8 IK E283 001GB ...

Reviews: