IK-E283-001GB 

 

Such an operation test can be carried out using a heat detector tester.  

A thermistor fault (short circuit or disconnection) is revealed by the detector and a fault signal is sent 
to the control panel. Any damaged detectors should be passed to the manufacturer (Polon-Alfa, 155, 
Glinki Street, PL 85-861 Bydgoszcz, Poland) for repair. 

Note:

 The detector dismantling by the user, installer or maintenance technician is forbidden! Only a 

skilled installer is authorised to mount the detectors. 

 

7  

DETECTOR INSTALLATION 

The  TUN-4046  heat  detectors  are  installed  (height,  arrangement)  according  to  the  Scientific  and 
Research  Centre  for  Fire  Protection  guidelines.  They  operate  in  loop-shaped  lines,  in  loop-shaped 
lines with straight branches, or in radial detection lines of the POLON 4000 and POLON 6000 system 
(see the POLON 4000 and POLON 6000 system manual).  

The  detectors  are  installed  in  the  40  model  range  bases.  A  detection  line  connection  method  is 
presented in the G-40 base installation and maintenance manual. An additional optical alarm signal 
of  a  detector  or  a  group  of  detectors  can  be  obtained  by  connecting  the  WZ-31  alarm  actuation 
indicator.  

Alarm system cables are routed in accordance with low voltage system (below 42V) regulations as in 
force. 

ATTENTION 

  The  detectors  should  not  be  installed  in  premises  of  corrosive  atmosphere  that 

contains caustic gases and vapours as well as high dust level. Steam condensation on the detectors 
is inadmissible. 

 

8  

STORAGE AND TRANSPORTATION 

8.1 Storage 

The TUN-4046 detectors should be kept in closed rooms free of any caustic gases and vapours at the 
temperature b0 

°C 

and +40 

°C,

 and relative humidity not exceeding 80 % at +35 

°C

In  the  time  of  storing,  the  detectors  should  not  be  exposed  to  either  direct  sunlight  or  heat  from 
heating equipment. 

The detectors storage period in transportation packing should not exceed 6 months. 

8.2 Transportation 

The TUN-4046 detectors can be carried in closed transport means spaces, in packing that meets the 
requirements  of  transportation  regulations  in  force. The  temperature  during  transportation  should 
not  be  lower  than  -

40  °C and  higher  than  +70  °C

,  and  relative  humidity  should  not  be  higher  than 

95% at + 45 

°C or 80% at +70 °C.

  

 
 

Summary of Contents for TUN-4046

Page 1: ...STATE UNIVERSAL HEAT DETECTOR TUN 4046 POLON 4000INTERACTIVE FIRE DETECTION ANDALARM SYSTEM _________________________________________________________________________________ INSTALLATION AND MAINTENANCE MANUAL IK E283 001GB Edition IIIC ...

Page 2: ...007 The features technical parameters above that exceeds the requirements of the aforementioned standards are confirmed by the Manufacturer Declaration of Performance has been issued for TUN 4046 The certificate and the Declaration of Performance can be downloaded from www polon alfa pl web site Read the manual carefully before the detector assembling and commissioning Any nonconformity with the i...

Page 3: ...S Operating voltage 16 5 V 24 6 V Maximum quiescent mode current consumption 150 µA Detector class according to PN EN 54 5 standard A1 A2 B A2S BS A1R A2R BR Maximum installation height 7 5 m Maximum supervised area 30 m2 Other parameters acc to PN EN 54 5 standard Allowable relative humidity up to 95 at 40 C Minimum operating temperature 25 C Dimensions without base Ø 115 mm x 43 mm Mass without ...

Page 4: ...e consisting of a temperature sensitive resistor thermistor The thermistor protruding above the detector casing is located in the central point and protected against mechanical damages by a basket The detecting module is fastened to a printed board that contains all electronic elements and the detector operation monitoring processor The detector shape and construction enable free ambient air flow ...

Page 5: ...on the alarm mode is indicated with pulse red light emitted by the signalling diode The fault mode technical alarm and short circuit isolator actuation are signalled with yellow flashes of the illuminating diode The detector is furnished with a possibility to choose a way of reaction in the installation place pursuant to a given class It is the TUN 4046 heat detector so called operation mode A cho...

Page 6: ...e manual An additional optical alarm signal of a detector or a group of detectors can be obtained by connecting the WZ 31 alarm actuation indicator Alarm system cables are routed in accordance with low voltage system below 42V regulations as in force ATTENTION The detectors should not be installed in premises of corrosive atmosphere that contains caustic gases and vapours as well as high dust leve...

Page 7: ...IK E283 001GB 7 Fig 2 Clamps of base interoperating with TUN 4046 plug IK E283 001GB 06 2011 10 2021 ...

Page 8: ...8 IK E283 001GB ...

Reviews: