IK-E287-001GB 2
1
PURPOSE
The
G
‐
40
detector
base
is
designed
for
the
connection
of
40
model
range
detectors
in
the
detecting
lines
of
conventional
control
panels
or
4043
and
4046
model
range
detectors
in
the
detecting
lines
of
the
POLON
4000
series
addressable
control
panels.
The
bases
are
intended
for
connecting
fire
detection
line
wires
routed
on
the
wall
plaster
(surface
mounting)
or
under
it
(semi
‐
flushed
mounting)
–
the
wires
are
placed
in
a
special
duct
of
max
height
at
10
mm).
The
G
‐
40
detector
bases
are
dedicated
for
dry
ceiling
mounting.
In
order
to
install
the
G
‐
40
base
on
a
ceiling
where
steam
condensation
occurs
or
when
it
is
mounted
on
horizontal
suspension
strands,
additional
PG
‐
40
base
industrial
footing
should
be
used.
The
PG
‐
40
base
industrial
footing
is
dedicated
for
connection
to
detection
line
wires
(the
wire
is
placed
inside
a
duct
of
max
external
diameter
at
Ø18
mm)
routed
on
the
plaster
(surface
mounting).
It
is
possible
to
utilise
the
G
‐
40
base
as
a
suspended
one
using
the
interconnecting
PG
‐
40
base
industrial
footing
equipped
with
the
PG7
sealing
gland
and
the
PSGW
ceiling
suspended
base.
The
suspended
part
of
the
base
should
be
mounted
on
a
4
‐
cord
cable
of
2
x
2
x
0.8
size.
Both
the
PG7
sealing
gland
and
the
PSGW
ceiling
suspended
base
are
not
standard
equipment
of
the
base
and
should
be
ordered
separately.
In
the
case
of
the
G
‐
40
base
installation
in
places
where
risk
it
can
be
endangered
by
a
mechanical
damage
(i.e.
sports
hall
–
ball
strike,
low
rooms
–
hit
with
a
ladder)
it
is
recommended
to
use
the
special
OZ
‐
40
protection
cover.
Additionally,
it
is
possible
to
fix
the
P
‐
40
special
masking
ring,
ordered
separately,
in
order
to
mask
the
base
visible
part.
Note:
If
the
G
‐
40
base
in
mounted
in
the
PG
‐
40
industrial
footing,
the
P
‐
40
masking
ring
is
not
applicable.
2
TECHNICAL
SPECIFICATIONS
G
‐
40
DETECTOR
BASE
Detectors
interoperating
with
G
‐
40
base
40,
4043
and
4046
model
range
detectors
Diameter
of
detection
line
wires
Ø
4.5
÷
Ø
5.5
mm
Max
diameter
of
cable
wires
≤
1mm
Mass
≤
0.1
kg
Dimensions
Ø
107
mm;
height
=
28.5
mm
Fastening
holes
spacing
63
mm
PG
‐
40
BASE
INDUSTRIAL
FOOTING
Interoperating
base
G
‐
40
base
Detection
line
wire
diameter
Ø
4.5
÷
Ø
5.5
mm
Mass
≤
0.1
kg
Dimensions
Ø
112
mm;
height
=
26
mm
Height
(PG
‐
40
with
G
‐
40)
43
mm
Fastening
holes
spacing
127
mm