background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

MEA244-1_DBL_LST_EN_0823.PDF • PAGE 1

A

Building Safety. Building Security.

Description

•   ADM loop technology with 

System Sensor/200 protocol

•   4 independent line-monitored inputs
•   4 independent outputs with patented 

monitoring of line resistance and

load resistance

•   Optimized for use in extinguishing 

systems

•   Supply supervised for undervoltage

The Multi Module MEA244-1 has been designed espe-

cially for use in extinguishing systems. It has 4 indepen-

dent inputs for connection of contact detectors, and 4 

independent, powerful outputs for actuation of external 

control devices.

The inputs are monitored to detect wire breakages and 

short circuits of the connection leads. On the outputs 

the internal resistances of the control devices and the 

line resistances are monitored separately. An automatic 

calibration procedure, which gets started by pressing 

a key during commissioning, determines the reference 

values  of  both  resistances.  The  patented  method  of 

multiple monitoring makes the reliable detection of line 

or load faults as well as contact corrosion possible.

The  multi  module  is  used  as  loop  element  with  inte-

grated dual-isolator, in an ADM loop with System Sen-

sor/200 protocol. The module occupies 8 consecutive 

addresses on the ADM loop. During commissioning, the 

base address, which is assigned to input 1, gets ente-

red using a key, all further addresses are automatically 

assigned by the module.

The MEA244-1 and the connected control devices are 

supplied  through  an  external  24V  power  supply.  The 

supply voltage gets supervised for undervoltages. If the 

voltage drops below the threshold of the undervoltage 

detection, then this event is automatically signalled to 

the control panel, via the loop, as fault of all four out-

puts. Each input and each output has a status LED.

The multi module is available in two versions:

•   The MEA244-1/TR has been designed for mounting 

on a DIN rail,

•   the MEA244-1/E can be mounted in a control panel 

using the supplied mounting spacers.

Reviews: