3.
Technical data
Table 3.1 Control Panel Technical Specification
POWER SUPPLY
Main supply voltage
10% - 15%
The frequency of the main supply voltage
47 ... 63Hz
Maximum supply current
150mA
Backup power supply source
12V 2.3Ah Battery
Current drawn from the batteries during the stand-by (control panel) < 100mA
POLON 6000 system addressable detection line current consumption < 0.6mA
INPUTS
LK1-LK4 control lines
Typical 0.3mA
3 + 2 (short circuit and opening)
Control current value (supervision mode)
Number of differentiated input states
Detection line
16
50mA / 2 x 45
Ω
20mA / 2 x 100
Ω
22mA / 2 x 75
Ω
40
Ω
300nF
100k
Ω
Maximum number of detectors in a detection line
Maximum load current for detection line / Maximum resistance of
the line wires depending on jumper settings:
- jumper S1 (S2) in position 1-2
- jumper S1 (S2) in position 2-3
- jumper S1 (S2) in position 2-3
The maximum line wires resistance between consecutive elements:
The maximum allowable line wires capacity:
Minimum insulation resistance of installation wiring:
OUTPUTS
External power supply line:
12VDC +5% -5%
500mA
External power supply line voltage
Continuous current from external power supply line
PK1-PK4 relay outputs
8A/ 250VAC
8A/ 30VDC
NO/NC contact current-voltage carrying capacity:
Cut-off valve control output:
12V
11A
from 0.2 to 1 second
from 10 to 60 seconds
Output voltage:
Maximum output current:
Control pulse time (programmable)
Minimum time between control pulses (programmable)