6
ID-E364-001
2.
Control panel structure and assemblage
CDG 6000 control panel requires 12V 2.3Ah lead-acid battery for correct operation. The battery is
placed inside the enclosure. Battery maximum external dimensions are as follows: 178 x 34 x 64mm.
The control panel can cooperate with PSG-6000 series gas detectors. The control panel detection line
may include up to 16 detectors of different types.
Table 1: PSG-6000 series detectors selection.
Detected Gas
CNG
(natural gas)
LPG
(propane
–
butane)
CO
(carbon oxide)
Model
PSG-6001
PSG-6002
PSG-6003
PSG-6103
Sensor Model
MSG-6001
MSG-6002
MSG-6003
MSG-6003
Sensor Type
semiconductor
semiconductor
electrochemical
electrochemical
Sensor
power
supply
External 9-30V
External 9-30V
External 9-30V
From detection line
The detectors connected with the control panel may be powered with external power supply or 12V
power supply line provided in the control panel for the user.
The control panel may additionally be fitted with MKA-60 module. This module expands the control
panel capabilities with ACOM 6.0 functionality. This functionality allows for direct cooperation of the
control panel with POLON 6000 fire alarm systems.
2.1.
Components layout in the control panel
Fig. 2.1.1 CDG 6000 control Panel
–
top view