ID-E364-001
17
6.
Detection line input
The CDG 6000 control panel may directly cooperate with the POLON6000 system. The gas detection
control panel may be connected to the POLON6000 fire alarm system detection line with additional
module MKA-60. LDA connector is provided for this connection. The LDA connector is described in
the following table.
Name
Purpose
WE+
WE-
Detectors line input
WY+
WY-
Detectors line output
E
Display input
6.1.
Battery connectors
The CDG 6000 control panel requires lead-acid battery for its correct operation. No connected
battery or a faulty battery results in fault signalization.
The battery in the control panel provides closing pulse for the cut-off valve. Inoperable battery
prevents valve activation.
Use only original wire set equipped with fuse socket to connect the battery to the control panel.
Battery specification:
Parameter
Value
Nominal voltage
12V
Capacity
2.3Ah
Maximum dimensions
length 180 x height 40 x
width 60
The battery must be definitely disconnected for storage of the control panel.