20
ID-E364-001
7.1.1.
Detectors configuration
In order to configure detects the line should be automatically configured. This procedure detects all
detectors connected with the control panel. To start the automatic configuration press
”
Automatic configuration
”
button. This procedure runs until the
”
Automatic configuration
”
button is
pressed again.
Upon the procedure completion the list should include all detectors connected with the control
panel. Click each item to display detailed detector information in the right side of the dialog box.
Furthermore, set the required sensor type for each detector. During operation, the control panel
continuously tests whether functional sensor of the required type is placed in each base.
Fig. 7.1.1.1 Configuration dialog box with an example of detector list.