Politec S.r.l. | Manual Ales – Ver. 1.7.2
11
7.
SETTING TIME
You can adjust the operating time of the optics such that the system goes into alarm, depending on usage and
the location where it is installed in order to avoid false alarms.
CONFIGURATIONS:
Standard (t = 50 ms)
Intercept run
t = 250 ms
Pets disqualification
t = 500 ms
Wall application
t = 750 ms
Particular aplication
TIME CHOICE
Press the TEST button and perform the alignment.
When alignment is performed, press the TEST button to exit the alignment mode and wait for the two
consecutive beep of the buzzer.
If you need the standard 50 ms delay time is not necessary to continue to the next step but wait for the
confirmation BEEP at the end of the 5 seconds.
Re-press the TEST button within 3 seconds at a time until you hear two consecutive BEEP to activate
the mode of action 250 ms, continue to press the TEST button until you hear three consecutive BEEP
and activates the mode of action 500 ms. And 'possible to obtain the means of intervention 750ms taking
further down the TEST button until the fourth consecutive BEEP.
To reset the time back to the first point of intervention.