8
PG2021 Global HAHU-VP-ECM-005
Product range
: HAHU-4R+1-P-EC 4-row coil for cooling and 1-row coil for heating 4-pipe with EC motor(s)
HAHU-4R+1-
[Size]
-P-EC
200
300
400
600
800
Unit configuration
Configuration
4 pipes
Number of Fan Blowers
1
2
Power supply (V/Ph/Hz)
220~240/1/50 or 60
P
e
rf
o
rm
a
n
ce
D
a
ta
Air
Air flow
H
m3/hr
2422
3304
4228
6608
8457
M
2058
2808
3594
5617
7188
L
1453
1982
2537
3965
5074
External Static
Pressure
H
Pa
100
M
100
L
100
Cooling
Total Cooling
capacity
H
kW
16.8
22.2
29
43.7
55.1
M
14.8
19.7
25.6
38.8
48.7
L
11.4
15
19.4
29.5
36.8
Sensible cooling
capacity
H
11.8
15.8
20.4
30.9
39.1
M
10.3
13.9
17.8
27.2
34.2
L
7.8
10.4
13.3
20.4
25.6
Heating
Heating
capacity
H
kW
13.8
18.2
23
33.5
42
M
12.3
16.1
20.4
29.7
37.3
L
9.4
12.3
15.4
22.7
28.2
Sound
Sound Pressure
dB(A)
62
66
72
71
75
Sound Power
71
75
81
80
84
Electrical
Power Input
W
375
501
505
1001
1005
Current
A
1.63
2.17
2.17
4.34
4.34
Hydraulic
Cooling Water
Flow Rate
H
L/h
2879
3802
4964
7498
9437
M
2542
3374
4389
6654
8344
L
1954
2566
3322
5060
6316
Cooling
Pressure Drop
H
kPa
25.5
15.5
27.3
62.7
48.6
M
20.4
12.5
21.9
50.6
38.9
L
12.7
7.6
13.3
30.9
23.6
Heating Water
Flow Rate
H
L/h
1186
1555
1970
2875
3599
M
1053
1378
1751
2546
3198
L
804
1053
1322
1946
2415
Heating
Pressure Drop
H
kPa
39.6
10.6
18.2
40.2
22
M
32
8.5
14.7
32.3
17.8
L
19.7
5.2
8.9
19.9
10.7
Cooling Water Content
L
7.38
9.12
10.85
12.59
15.19
Heating Water Content
1.845
2.28
2.715
3.15
3.8
Construction and Packing
Data
Cooling Water
Connections
In
inch
1 1/4”
Out
Heating Water
Connections
In
1”
Out
Condensate Drainage
Connection
inch
1”
Dimensions
L
mm
1280
1480
1680
1880
2180
W
1120
H
640
Net Weight
kg
155
177
195
232
264
Conditions:
a. Cooling mode:
b. Heating mode:
- Return air temperature: 27C DB/ 19C WB.
- Inlet/ outlet water temperature: 7C/ 12C.
- Air temperature: 20C.
- Water inlet/ outlet temperature: 65/55C.
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz