![Polar Air HAHU-200 Installation, Operation & Service Manual Download Page 21](http://html1.mh-extra.com/html/polar-air/hahu-200/hahu-200_installation-operation-and-service-manual_1571089021.webp)
20
PG2021 Global HAHU-VP-ECM-005
B . 3 .
I n s t a l l a t i o n P r o c e d u r e s
1.
The unit is designed to be installed in a concealed ceiling. Installation and maintenance should be performed by qualified
personnel who are familiar with local codes and regulations, and are experienced with this type of appliance.
2.
Please refer to the pictures below for installation procedure.
Tie rod
Nut
Washer
Bracket
Vibration damper
Washer
Nut
Nut
B
CEILLING
DRAIN PIPE
>200mm
-
>600mm
_
H2
H
1
H1>
1
2
*ESPmax/9.81
H2>ESPmax/9.81
CAUTIONS
Make sure the top of he unit is level after installation. The drain pan is designed with
a slight gradient to facilitate drainage.
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz