6
PG2021 Global HAHU-VP-ECM-005
A . 2 .
G e n e r a l S p e c i f i c a t i o n s
Product range
: HAHU-4R-V-EC 4-row coil 2-pipe with EC motor(s)
HAHU-4R-
[Size]
-V-EC
200
300
400
600
800
Unit
configuration
Configuration
2 pipes
Number of Fan Blowers
1
2
Power supply (V/Ph/Hz)
220~240/1/50 or 60
P
e
rf
o
rm
a
n
ce
D
a
ta
Air
Air flow
H
m3/hr
2329
3238
4166
6475
8332
M
1980
2752
3541
5504
7082
L
1398
1943
2500
3885
4999
External Static
Pressure
H
Pa
120
M
120
L
120
Cooling
Cooling capacity
H
kW
16.3
21.9
28.5
43.1
54.3
M
14.4
19.4
25.4
38.2
48.3
L
11.0
14.8
19.1
29.2
36.4
Sensible cooling
capacity
H
11.4
15.5
20.1
30.5
38.5
M
10.0
13.6
17.6
26.7
33.9
L
7.6
10.3
13.2
20.1
25.3
Heating
Heating capacity
H
kW
19.5
26.3
34.3
51.8
65.1
M
17.3
23.3
30.5
45.8
57.9
L
13.2
17.8
23.0
35.0
43.7
Max. EH capacity
kW
4.5
6
7.5
9
9
Sound
Sound Pressure
dB(A)
62
66
72
71
75
Sound Power
71
75
81
80
84
Electrical
Power Input
W
375
501
504
1001
1005
Current
A
1.63
2.17
2.17
4.34
4.34
Hydraulic
Cooling Water
Flow Rate
H
L/h
2787
3749
4892
7392
9301
M
2467
3321
4351
6548
8272
L
1892
2535
3280
4999
6236
Cooling Pressure
Drop
H
kPa
24
15.1
26.6
61.1
47.3
M
19.3
12.1
21.5
49.1
38.3
L
12
7.5
13
30.2
23
Heating Water Flow Rate
L/h
Same As "Cooling Water Flow Rate"
Heating Pressure
Drop
H
kPa
21.6
13.6
23.9
55.0
42.6
M
17.4
10.9
19.4
44.2
34.5
L
10.8
6.7
11.7
27.2
20.7
Water content
L
7.38
9.12
10.9
12.6
15.2
Construction
and Packing
Data
Water
Connections
In
inch
1 1/4”
Out
Condensate Drainage
Connection
inch
1”
Dimensions
L
mm
1280
1480
1680
1880
2180
W
1120
H
640
Net Weight
kg
150
175
186
223
255
Conditions:
a. Cooling mode:
b. Heating mode:
- Return air temperature: 27C DB/ 19C WB.
- Inlet/ outlet water temperature: 7C/ 12C.
- Return air temperature: 20C.
- Inlet water temperature: 50C.
- Same water flow as cooling mode.
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz