D. Installation - Cooling
Cooling working On-Off (with On time= 0
m
.00)
When set a
On time = 0
m
.00
s
the Cooling
works as a normal On-Off system.
COOL
ON*
OFF
Ventilation
temperature probe
* Controlled by
ON
MAX HUMIDITY
COOL 1 BLOCK
if Humidity control is
present.
Cooling temp. set
This set can be either an absolute or a
relative setting according to what has
been selected in the previous option
Cooling setting mode.
If
Relative=
value setting related to
Ventilation
set
(Settings > Climate
see par. C.1)
.
Temperat.
differ.
Humidity Block on Cooling system
In case %RH Indoor Humidity goes above the max allowed value.
MAX
HUMIDITY
BLOCK
COOL
ON*
OFF
Cooling humidity set
*Conditions ON
COOL
if Humidity control is
present.
Ambient
humidity
Humidif.
differ.
If
On time
is different from
0
m
.00
s
the
Timer band
Cooling is working by timer (On and Off times
are as set in
On time
and
Off time)
.
In the case the indoor % humidity goes above the maximum allowed value
,
Timer band
cooling will
work continously (without temporization), in case %RH Indoor Humidity goes above the max allowed
value.
Cooling temporized working
(with On time> 0
m
.00
s
, Off time> 0
m
.00
s
)
OFF
OFF
ON*
Timer band
COOL
1
* Controlled by
ON
MAX HUMIDITY COOL BLOCK
if Humidity control is present.
ON*
OFF
ON*
OFF
ON*
Cooling temp. set
Temperat.
differ.
This set can be either an absolute or a relative setting
according to what has been selected in the previous option
Cooling setting mode.
If
Relative=
value setting related to
Ventilation
set
(Settings > Climate
see par. C.1)
.
Ventilation
temperature probe