D. Installation - Ventilation
Sets the outdoor temperature which activates the
‘Outdoor
temperature block’.
Maximum ventilation allowed when ‘Outdoor temperature block’
is
activated (when ventilation is made in steps).
Outdoor temp. set
(Range: -30.0°...
10.0
°...50.0°)
Max. step ventilat.
(Range: 0...
16
)
D.1.3.6.6 Max. for outdoor temperature
Path:
Home
>
Installation>
Climate>
Ventilation>
Conditionings>
Max. for outdoor temp.
This function allows to set a safety block on maximum ventilation.
*
OUTDOOR TEMPERATURE BLOCK
can influence the maximum ventilation step.
Below a certain external temperature (
Outdoor temp. set
) the maximum ventilation can be limited
(
Max. step ventilat
).
OFF
MAXIMUM
VENTIL.
BLOCK
Outdoor
temperature
ON*
Outdoor temp. set
Time (hours:mins) when the night time period starts.
Time (hours:mins) when the night time period ends.
Variation of the
Ventilation
se during the night time period (+ or -).
Night start time
(Range:
0
h
.00
m
...23.
h
59
m
)
Night end time
(Range:
0
h
.00
m
...23.
h
59
m
)
Night set variation
(Range: -30.0°...
0.0°
...30.0°)
D.1.3.6.7 Night ventilation change
Path:
Home
>
Installation>
Climate>
Ventilation>
Conditionings>
Night ventilat. change
By this conditioning you can adjust the nightime Ventilation set of temperature. As option you can also
change the nightime Heating set of temperature
(par. D.1.1.2.1 Heating conditioning).
Note: when setting
00:00
as start and end time, night ventilation range is excluded.
Differential
fixed=1.0°