68
Commands
Link Manager Manual
Analog
(A0.00305,0.00000,%,2,0,0)
29
CounterAnalog
3
State
Integer
Analog
(STrans.,Open,Closed,Error,0)
(I1,0,count,0,0)
(A0.00305,0.00000,%,2,0,0)
30
Humidity/
Temperature
(Point Humid2)
2
Analog
Analog
(A0.0244,0.0000,%RH,1,0,0)
(A0.0549,-40.0000,F,1,0,0)
31
Dwell
3
State
Integer
Analog
(SBlocked,NotPres,Pres,na,0)
(I1.000,0,count,0,0)
(A1.000,0.000,sec,0,0,0)
The “CSC” command clears all the entries in the sensor table. This includes both event
information for all sensors and I/O points and sensor setup. If the Activity Log has
entries, Link Manager will give an error “16” when processing the “CSC” command.
The “CSCF” command clears the Activity Log before clearing the entries in the sensor
table.
The “CSD” command removes a single sensor from the sensor table. If the Activity Log
has entries, Link Manager will give an error “16” when processing the “CSD” command.
The “CSDF” command clears the Activity Log before clearing the entries in the sensor
table.
If a sensor has been set up with the wrong type of I/O Point Type, the Link Manager
will display “BAD CFG” for the I/O data in the I/O Status page and the response to
the “D” command. If this condition occurs, you will have to delete the setup entry in
the sensor table.
Sensors of type unknown can be added through Auto Add Mode but cannot be set
using the “CSS” command.
Examples
Command:
CSS1
,7D000000059A9328,1Humid(A1,0,%RH,0)(A1.8,32.0,degF,1),2
Response: CSS1
Remarks: configure row 1 in the sensor table as a Humidity/Temperature
sensor. “7D000000059A9328” is the
serial number. “1Humid” is the
sensor label. “(A1,0,%RH,0)”
is the
first I/O point which is Analog
type and is the humidity portion of the sensor. “(A1.8,32.0,degF,1)”
is the second I/O point which is an Analog type and is the temperature
portion of the sensor.
Command:
CSR1
Response:
CSR1,2,7D000000059A9328,1Humid(A1,0,%RH,0,0)(A1.8,32.0,degF,1,0)
Command:
CSS1
,7D000000059A9328,HmdA23-2(A1,0,HUM,0)
(A1.8,32.0,FAR,1),2
Response: CSS1
Command:
CSR2
Response: CSR2,8,87000000002D0A27,1AngD(A0.02,0.00,%,2,0)(DY,0)
Command:
CSD2
Response: CSD2
Remark: Clear the second sensor in the sensor table