16
Point Sensor Utility
Link Manager Manual
Set the utility to use the Digi XBee 900 radio. From the main menu, select Options
and Radio Type. Select “Digi Xbee 900/2.4”.
Point Sensor Utility Usage
Connect the USB Programming interface into the sensor and then from the Setup tab
click on the Retrieve button to retrieve the sensor’s settings.
From the Setup tab, set the Transmit Period, Tries, Logging Period, Alarms and the
ID Info.
Click the Update button (in the Setup tab) to update the sensor with the latest settings
and also set the special addressing mode for the sensor radio.
Disconnect the USB Programming interface. The sensor is now ready to be used
with a Link Manager.
Advanced Setup
You may need to set the Point Sensor to use another radio Hop Table under the
following circumstances:
1.
Having interference issues using the default Hop Table (3).
2.
Have more than one Link Manager within radio range and want to isolate
the radio networks between Link Managers.
To change the Hop Table number, in the Point Sensor Utility , go to the Help menu
and then select “Utility Folder Paths” and then “Explore Setup”. The utility will
open a text editor showing the Point Sensor Utility settings. Add the line
“XSCSNHopTable=
n
” to the [Settings] section where “n” is a number from 0 to 6.
Here is an example: