Name

Value range

Description

rES.H

Reset maximum value

0

Interface only

2

di1 switches

7

Limit 1 switches

8

Limit 2 switches

9

Limit 3 switches

10

Enter/Inc keys switch

Ü

11

Enter/Dec key switch

Ü

rES.I

Reset Integrator

0

Interface only

2

di1 switches

7

Limit 1 switches

8

Limit 2 switches

9

Limit 3 switches

10

Enter/Inc keys switch

Ü

11

Enter/Dec key switch

Ü

CAL.t

Calibration test (activation bridge resistance change)

0

Interface only

2

di1 switches

7

Limit 1 switches

8

Limit 2 switches

9

Limit 3 switches

10

Enter/Inc keys switch

Ü

11

Enter/Dec key switch

Ü

ZEro

Zero setting

0

Interface only

2

di1 switches

7

Limit 1 switches

8

Limit 2 switches

9

Limit 3 switches

10

Enter/Inc keys switch

Ü

11

Enter/Dec key switch

Ü

fDI1

Forcing of the digital input (only visible with BlueControl

Ò

!)

0

not active

1

The value for this input is defined via interface.

Configuration level

SG 45

Configurations

42

Summary of Contents for SG45-115-00000-000

Page 1: ...PMA Proze und Maschinen Automation GmbH Transmitter UNIFLEX SG45 SENSE INP EX EX 2 kg SG UNIFLEX UNIFLEX SG 45 SG 45 Operating manual English 9499 040 82311 valid from 10 2009...

Page 2: ...Caution ESD sensitive components Caution Read the operating instructions Read the operating instructions Note 2008 PMA Proze und Maschinen Automation GmbH Printed in Germany All rights reserved No par...

Page 3: ...4 3 Switch over with the enter key 18 5 4 4 Slave pointer function 19 5 4 5 Selecting the units 19 5 4 6 Extended operating level 20 6 Functions 21 6 1 Measuring input INP 21 6 2 Input scaling 22 6 3...

Page 4: ...onfigurations 35 8 Parameter level 41 8 1 Parameter survey 41 8 2 Adjustment 41 8 3 Parameters 42 9 Installation and calibration 43 9 1 Initial setting SEt 43 9 2 Calibration CAL 44 9 3 Scaling SCAL 4...

Page 5: ...ompact construction only 22 5 mm wide Clips onto top hat DIN rail Plug in screw terminals or spring clamp connectors Dual line LC display with additional display elements Process values always in view...

Page 6: ...General 6 SG 45...

Page 7: ...t the following information is taken into account Ensure that the supply voltage corresponds to the specifications on the type label All covers required for contact protection must be fitted If the co...

Page 8: ...ervice under PMA Proze und Maschinen Automation GmbH Miramstra e 87 D 34123 Kassel Tel 49 0 561 505 1257 Fax 49 0 561 505 1357 e mail mailbox pma online de 2 2 Cleaning g The cleaning of the front of...

Page 9: ...may be operated only in environments for which it is suitable due to its protection type a The housing ventilation slots must not be covered a In plants where transient voltage peaks are susceptible...

Page 10: ...conductors Spring clamp terminals for max 2 5 mm 2 conductors g Before handling the connectors the unit must be disconnected from the supply voltage Tighten the screw terminals with a torque of 0 5 0...

Page 11: ...als 15 16 must not be used 2 Connecting input INP1 Input for strain gauge in 4 and 6 wire connection or for melt pressure sensors with without calibration shunt a Excitation voltage for bridge EXITATI...

Page 12: ...s with a common terminal OUT1 terminals 17 18 OUT2 terminals 17 14 5 Connecting output OUT3 Universal output d current 0 20mA terminals 11 12 e voltage 0 10V terminals 12 13 6 Connecting the bus inter...

Page 13: ...tion diagram Example Electrical connections SG 45 Connecting diagram 13 Device1 bct Connecting plan Terminal connector 1 Terminal connector 2 Terminal connector 3 Name Description Name Description Nam...

Page 14: ...ense SENSE INP EX EX Example Connection load cell with 4 or 6 wire bridge 1 4 EX 5 INP 6 INP 3 SENSE Excitation Excitation Ausgang EX R CAL SENSE INP EX EX Example Connection of a melt pressure sensor...

Page 15: ...ent a The measurement inputs are designed for measurement of circuits which are not connected directly with the mains supply CAT I The measurement inputs are designed for transient voltage peaks up to...

Page 16: ...Electrical connections 16 UL approval optional SG 45...

Page 17: ...ith optional system interface red limit value 1 active red blinking instrument fault configuration mistake 8 Display elements active as bars 9 Status of switching output OUT1 active 0 Status of switch...

Page 18: ...he pass number is done via BlueControl Individual parameters which must be accessible without pass number or from a disabled parameter level must be copied into the extended operating level Factory se...

Page 19: ...alues signals dependent on the inputs e g Inp1 Inp2 display value Out3 also indicate FAIL 5 4 3 Switch over with the enter key By using the enter key different values can be called in display 2 1 Disp...

Page 20: ...put rES H can be determined during configura tion Deleting the minimum and maximum values is possible also via interface g When de energizing UNIFLEX SG 45 the minimum and maximum values are deleted g...

Page 21: ...eans of the BlueControl engineering tool For this select entry Operation level in the Mode selection menu Further information is given in the on line help of the engi neering tool Press key to display...

Page 22: ...Operation SG 45 Displays in the operating level 22...

Page 23: ...o the sensor 6 wire Bridge supply mV input calibration output for defined change of the bridge resistance Using a built in switch a known resistor is switched in parallel to one of the 4 bridge resist...

Page 24: ...physical quantity g The Parameters InL OuL InH and OuH are always visible These are created during calibration Parameters InL and InH determine the input range Example with InL 4 and InH 10 means that...

Page 25: ...points Each segment point comprises an input In 1 In 32 and an output Ou 1 Ou 32 These segment points are interconnected automatically by straight lines The straight line between the first two segment...

Page 26: ...dependent of the selected input function The selected controller output reaction on sensor fault configuration FAIL is omitted With factory setting the substitute value is switched off a Before activa...

Page 27: ...ent value Effective value The tare function is enabled during configuration Func r Fnc 3 1 Dependent on configuration the tare function can be activated by digital input di1 a limit value a key combin...

Page 28: ...i rES I the integrator can be reset via Digital input di1 Key combination Enter increment key keep the Enter key pressed and actuate the increment key Limit values Limit1 to Limit3 Example 1 A flow in...

Page 29: ...values Lim 1 Lim 3 has 2 trigger points H x Max and L x Min which can be switched off individually parameter OFF The hysteresis HYS x of each limit value is adjustable Input value monitoring is as sh...

Page 30: ...mit value is still exceeded Shorter alarms than the adjusted delay are ignored Signal change monitoring Another limit value processing function is signal change monitoring per minute Functions SG 45 L...

Page 31: ...st be specified in the error list or via the interface r page 36 g After power on or an engineering download an used input filter has an effect on the gradient of the input signal Therefore a valid al...

Page 32: ...alues are lost when switching off Number of switching cycles The output number of switching cycles can be monitored When reaching or exceeding the adjusted limit value signal InF 2 is activated in the...

Page 33: ...of the full input range 0 100 Out 0 100 Out 1 1200 Example output of a limited input range e g 60 5 63 7 C Out 0 60 5 Out 1 63 7 The output behaviour in the event of an input value error can be deter...

Page 34: ...or value input via interface or by means of an input value at extended operating level Forcing g This setting can be used also for e g testing the cables and units connected in the output circuit g Th...

Page 35: ...Return device to manufacturer E 2 Internal error resettable E g EMC trouble Keep measuring and supply cables separate Protect contactors by means of RC snubber cir cuits E 3 Configuration error reset...

Page 36: ...ply 1 measuring or sense lines FAIL on the process value display and FbF 1 in the error list are displayed Wrong polarity of supply sense and input signal lines FAIL on process value display and POL 1...

Page 37: ...rts In all other cases no reset will occur timeout abortion g If one of the operating levels was blocked in BlueControl reset to factory setting is not possible g If a pass number was defined via Blue...

Page 38: ...ayed and followed by automatic change to the next group g Return to the beginning of a group is by pressing the key for 3 sec g Please check all interdependent parameters for their validity Configurat...

Page 39: ...values Lim1 Lim3 Name Value range Description Fnc 1 Fnc 2 Fnc 3 Function of limit 1 2 3 0 Switched off 1 Measurement value 2 Measured value monitoring alarm status latch A stored limit value can be re...

Page 40: ...ol 0 not active 1 active fOut Forcing of the output only visible with BlueControl 0 not active 1 The value for this analog output is defined via interface Output Out 3 analog Name Value range Descript...

Page 41: ...1 switches 7 Limit 1 switches 8 Limit 2 switches 9 Limit 3 switches 10 Enter Inc keys switch 11 Enter Dec key switch tArA Tare function Function must be akctivated CONF FUNC Fnc 2 3 0 Interface only 2...

Page 42: ...ec key switch CAL t Calibration test activation bridge resistance change 0 Interface only 2 di1 switches 7 Limit 1 switches 8 Limit 2 switches 9 Limit 3 switches 10 Enter Inc keys switch 11 Enter Dec...

Page 43: ...frequency 50 Hz 1 Netfrequency 60 Hz D Unt Anzeigeeinheit Darstellung auf Display 0 no unit 3 4 bar 5 mbar 6 Pa 7 kPa 8 psi 18 mV 19 kg 20 g 21 t 22 Text of phys Unit preset via BlueControl 23 lb 24 N...

Page 44: ...1 Blocked T Dis2 Settings for text in display 2 max 5 digits only visible with BlueControl Enter the corresponding number of spaces for right adjusted display of less than 5 characters 1 Hold down th...

Page 45: ...eters can be adjusted with keys Stepping to the next parameter by pressing the key After the last parameter of a group donE appears in the display and the controller steps automatically to the next gr...

Page 46: ...rbandwidth Limit values Lim1 Lim 3 Name Value range Description L 1 1999 9999 lower limit 1 L 1 1999 off H 1 1999 9999 upper limit 1 H 1 1999 off HYS 1 0 9999 Hysteresis of limit value 1 dEL 1 0 9999...

Page 47: ...ibration the calibrating resistor at the sense connection is included automatically during calibration of the upper calibration point InH 1 OuH 1 1 Only purposeful for melt pressure sensors with integ...

Page 48: ...d calibration resistor an automatic switching of the calibration resistor is done For the first calibration SEtit is recommended to configure CAL M 1 S 47 InH 1 OFF Press keys p q to display the insta...

Page 49: ...donE End Operating level Note related to melt pressure sensor Adjust gradient 4mV V for 3 33mV V of the sensor Please note that the InL 1 and InH 1 values are displayed with a resolution of 4 digits...

Page 50: ...engineering from the controller SIM only yes yes basic diagnostic functions no no yes saving data file and engineering no yes yes printer function no yes yes online documentation help yes yes yes impl...

Page 51: ...pter for BluePort interface 9407 998 00001 BlueControl Mini www pma online de BlueControl with Basic licence rail line 9407 999 12001 BlueControl with Expert licence rail line 9407 999 12011 Versions...

Page 52: ...t and zero setting OUTPUTS RELAY OUTPUTS OUT1 OUT2 Contact type 2 normally open with common contact connection Max contact rating 500 VA max 250 V max 2A at 48 62 Hz ohmic load Min contact rating 6V 1...

Page 53: ...uration and parameter settings Permanent storage in EEPROM BLUEPORT FRONT INTERFACE Connection to the controller front via a PC adapter see Additional Accessories The BlueControl software enables the...

Page 54: ...for screw terminals V0 UL 94 for spring clamp terminals and bus connector Electrical safety Complies with EN 61 010 1 Over voltage category II Contamination degree 2 Protection class II Certification...

Page 55: ...ont view 16 Functions 21 33 I Input scaling 22 Input value monitoring 27 Installation hints 15 L Limit values 27 29 Linearization 40 M Maintenance 8 Maintenance manager 31 maximum value 19 minimum val...

Page 56: ...e PMA Proze und Maschinen Automation GmbH nderungen vorbehalten P O B 310 229 D 34058 Kassel Germany Sous r serve de toutes modifications Printed in Germany 9499 040 82311 10 2009 A4 unibind SW Druck...

Reviews: